16 DeviceNet 1732 ArmorBlock 16-Point I/O, Series A
Publication 1732D-IN002B-EN-E - January 2013
Refer to the device status indicator table for a description of the status indicators
Specifications
Device Status Indicators
Indicator
Status Description
Network status
Off
Device is not online:
- Device has not completed dup_MAC-id test.
- Device not powered – check module status
indicator.
Green
Device operating normally. As a Group 2 module, it
means that the module is allocated to a master.
Flashing green
Device is online with no connections in the
established state
Red
Critical link failure – failed communications module
Flashing red
Recoverable fault – an I/O connection has timed out
Module status
Off
No power applied to the device
Green
Device is online and has one or more I/O connections
in established state
Flashing green
Device needs commissioning due to missing,
incomplete, or incorrect configuration
Red
Critical fault – Device timed out or has an
unrecoverable fault
Flashing red
Recoverable fault – input or output short circuit
Auxiliary status
Off
No auxiliary power applied to the device
Green
Auxiliary power is applied to the device
I/O status
Off
I/O is not energized or is not valid
Yellow
I/O is energized and valid
DeviceNet 1732 ArmorBlock 16-Point I/O, Series A - 1732D-IB16M12M12,
1732D-IB16M12MINI, 1732D-16CFGM12M12, 1732D-16CFGM12MINI
Attribute
Value
Number of Inputs
16
Input type
61131-2 Type 3 compatible
Off-state input voltage, max
5V DC
Voltage, on-state input, max
30V DC
Voltage, on-state input, nom
24V DC
Voltage, on-state input, min
11V DC