Clx status indicator – controlbus status, Adapter mode – Rockwell Automation 1756-RIO ControlLogix Remote I/O (RIO) Communication Interface Module Installation Instr User Manual
Page 20

20 ControlLogix Remote I/O (RIO) Module
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
Adapter Mode
This table shows status in order of priority, highest first.
CLX Status Indicator – ControlBus Status
The CLX indicator displays the status of communication with the ControlLogix
processor.
Indicator
Status
Description
RIO
Red
A frame-receive error has been received in the last
second (CRC error, abort, or time-out). Indicator stays
red for one second after the error occurs.
Flashing red/off
One or more racks are not being scanned.
Flashing green/off
Configuration mismatch on one or more racks.
Green
All racks are being scanned and there are no
configuration mismatches.
Indicator
Status
Description
CLX
Green
The module has successfully processed a request
from the ControlBus backplane within the last five
seconds. All required connections are open.
Flashing green/off
Controlling Connection is open, but not all required
connections are open.
Yellow
Idle, no requests received from the backplane in the
last five seconds. No connections; empty
configuration.
Flashing yellow/off
Controlling Connection is not open.
Red
The module has returned a CIP error to a request from
the backplane within the last second. All required
connections are open.
Flashing red/off
The module has returned a CIP error within the last
second. All required connections are not open.