Controller components chapter 2 – Rockwell Automation 1772-LV,D17726.6.1 A and I MNL MINI-PLC-2/15 PROCESSO User Manual
Page 10
Controller Components
Chapter 2
2Ć5
Table 1.A
Module Reference Chart
Module
Cat. No.
Module's
Load on
System
Power
Supply
Keying Band
Positions
Between Nos.
Field
Wiring Arm
(Cat. No.
1771Ć )
ColorĆ
Coded
Label
AC/DC (120V) Input
DC (12Ć24V) Input
DC (48V) Input
Isolated AC/DC (120V) Input
Analog (8 bit) Input
Analog (12 bit) Input
1771ĆIA
1771ĆIB
1771ĆIC
1771ĆID
1771ĆIE
1771ĆIF
74mA
74mA
74mA
50mA
400mA
1.3A
4Ć6, 10Ć12
4Ć6, 14Ć16
4Ć6, 16Ć18
4Ć6, 28Ć30
4Ć6, 26Ć30
6Ć8. 22Ć24
4Ć6, 32Ć34
ĆWA
ĆWA
ĆWA
ĆWD
ĆWB
ĆWB
ĆWB
Red
Blue
Blue
Red
Pink
Pink
Pink
TTL Input
DC (24Ć28V) Input
Encoder/Counter (5V)
1771ĆIG
1771ĆIH
1771ĆIJ
122mA
74mA
1.4A
4Ć6, 34Ć36
4Ć6, 16Ć18
6Ć8. 18Ć20
4Ć6, 32Ć34
ĆWC
ĆWA
ĆWB
ĆWB
Pink
Blue
Brown
Brown
Encoder/Counter (12Ć24V)
1771ĆIK
1.4A
6Ć8, 20Ć22
4Ć6, 32Ć34
ĆWB
ĆWB
Brown
Brown
AC/DC (220/240V) Input
DC (5Ć30V) Selectable Input
Fast Response DC (12Ć24V)
Input
DC (12Ć24V) Driver Logic Input
Thermocouple Input
1771ĆIM
1771ĆIQ
1771ĆIT
1771ĆIV
1771ĆIX
75mA
150mS
74mA
74mA
2.0A
6Ć8, 30Ć32
6Ć8, 24Ć26
6Ć8, 32Ć34
8Ć10, 12Ć14
8Ć10, 18Ć20
8Ć10, 20Ć22
ĆWA
ĆWC
ĆWA
ĆWA
ĆWE
Red
Blue
Blue
Blue
Blue
Pink
Thermocouple Input Expander
AC (120V) Output
DC (12Ć24) Output
DC (48V) Output
Isolated AC (120V) Output
Analog (12 bit) Output
1771ĆIY
1771ĆOA
1771ĆOB
1771ĆOC
1771ĆOD
1771ĆOF
500mA
210mA
165mA
165mA
225mA
1.4A
8Ć10, 20Ć22
4Ć6, 12Ć14
4Ć6, 18Ć20
4Ć6, 20Ć22
4Ć6, 30Ć32
2Ć4, 6Ć8
4Ć6, 32Ć34
ĆWE
ĆWA
ĆWA
ĆWA
ĆWD
ĆWB
Pink
Orange
Green
Green
Orange
Yellow
Yellow
TTL Output
AC (220/240V) Output
Contact Output
Gray Encoder Input (8 bit)
MiniĆPLCĆ2/15 Processor
Communication Adapter
Communication Controller
Communication Controller
Data Highway Interface/Modem
Modem Interface
1771ĆOG
1771ĆOM
1771ĆOY
1771ĆDL
1772ĆLV
1771ĆKA
1771ĆKC
1771ĆKD
1771ĆKF
1771ĆKG
168mA
225mA
420mA
120mA
2.0A
1.2A
1.2A
1.2A
1.2A
1.0A
6Ć8, 10Ć12
6Ć8, 28Ć30
6Ć8, 16Ć18
4Ć6, 24Ć26
40Ć42, 54Ć56
4Ć6, 22Ć24
6Ć8, 12Ć14
4Ć6, 22Ć24
ĆWC
ĆWA
ĆWD
ĆWB
Gray
Orange
Orange
Brown
AC Input Fuse
A slow-blow fuse (Figure 2.2) is used to guard against overcurrent conditions
on the AC input line. The Power Supply is shipped with a 1-amp fuse in the
fuse holder for 120V operation. For 220/240V operation, a 0.5-amp fuse is
required and is included with the Power Supply.