Connect the devicenet cable – Rockwell Automation 1790D-XXXX DeviceNet Digital Base D-Shell Module CompactBlock LDX I/O Series B User Manual
Page 13

DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 13
Publication
1790-IN013A-EN-P - September 2006
1790D-0V16 Output Block Wiring Diagram
For sinking outputs, wire Com 0 and Com 2 to Field Power (+) 24V dc, and
Com 1 and Com 3 to Field Power (-) GND.
Note that all Com 0 and Com 2 are internally connected.
1790D-0W6 Relay Output Block Wiring Diagram
Wire pins 18 and 19 to Field Power (+) 24V dc.
Wire pins 36 and 37 to Field Power (-) GND.
Connect the DeviceNet Cable
Follow these procedures to connect the DeviceNet cable to the base
block. The DeviceNet connector is not supplied with the base block.
You must purchase the connector separately. These are the types of
connectors you order directly from Rockwell Automation.
• 1799-DNETCON - 5-position open style connector
• 1799-DNETSCON - 5-position open style connector with
locking screws
• 1799-DNC5MMS - 5-position open style to 12 mm connector
with locking screws
44169
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
COM0
O0
O1
O2
O3
O4
O5
O6
O7
COM2
O8
O9
O10
O11
O12
O13
O14
O15
COM1
COM0
COM0
COM0
COM0
COM2
COM2
COM2
COM2
COM0
COM0
COM0
COM0
COM3
COM2
COM2
COM2
COM2
44170
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
+24V
CH0
COM0
CH1
COM1
CH2
COM2
CH3
COM3
CH4
COM4
CH5
COM5
NC
NC
NC
NC
GND
GND
+24V