2 Sinking Input / 2 Output Module

Publication 1792D-5.25- January 1999

Specifications

Auxiliary Power

Indication

Status

None

No Auxiliary Power

Green
Solid

Auxiliary Power Present

I/O Status Indicators

Function

Module Status Indicator

Point Indicator

Condition

Outputs

Green
Green

None
Yellow

Output not energized
Output energized

Inputs

Green
Green

None
Yellow

No valid input
Valid input

2 Input / 2 Output Module - Cat. No. 1792D-2B2LP

Sinking Input Specifications

Max

Min

Inputs per block

2 - 3 wire or dry contact PNP

Sensor Source Current (per input)

100mA

-

On-state Voltage

25V dc

10V dc

Off-state Voltage

5V dc

On-state Current

10mA

2mA

Off-state Current

1.5mA

Sourcing Output Specifications

Max

Min

Outputs per block

2 labeled O0 and O1

Output Auxiliary Voltage

30V

10V

On-state Voltage Drop

1V

-

On-state Current

0.3A

-

Off-state Leakage

1.5mA

-

Module Current (all outputs)

0.6A

-

Surge Current - for 10ms,
repeatable every 2s

0.6A

-

No Load Sense Current (On-state)

0.18A

-

General Specifications

Indicators

Network Status - red/green
Module Status - red/green
Auxiliary Power - green
Point LED - yellow