beautypg.com

Rockwell Automation 1791-IOBB USER MANUAL User Manual

Page 23

background image

Configuring Your Block I/O for PLC

Family Programmable Controllers

Chapter 4

4Ć3

Table 4.B

PLC-3 and PLC-5/250 I/O Rack Addressing

I/O Rack

Switch Number

I/O Rack

Switch Number

Number 3

4

5

6

Number

3

4

5

6

0

On (Closed)

On (Closed)

On (Closed)

On (Closed)

10

On (Closed)

On (Closed)

On (Closed)

Off (Open)

1

Off (Open)

On (Closed)

On (Closed)

On (Closed)

11

Off (Open)

On (Closed)

On (Closed)

Off (Open)

2

On (Closed)

Off (Open)

On (Closed)

On (Closed)

12

On (Closed)

Off (Open)

On (Closed)

Off (Open)

3

Off (Open)

Off (Open)

On (Closed)

On (Closed)

13

Off (Open)

Off (Open)

On (Closed)

Off (Open)

4

On (Closed)

On (Closed)

Off (Open)

On (Closed)

14

On (Closed)

On (Closed)

Off (Open)

Off (Open)

5

Off (Open)

On (Closed)

Off (Open)

On (Closed)

15

Off (Open)

On (Closed)

Off (Open)

Off (Open)

6

On (Closed)

Off (Open)

Off (Open)

On (Closed)

16

On (Closed)

Off (Open)

Off (Open)

Off (Open)

7

Off (Open)

Off (Open)

Off (Open)

On (Closed)

17

Off (Open)

Off (Open)

Off (Open)

Off (Open)

Table 4.C

PLC-5 I/O Rack Addressing

I/O Rack Switch Number

I/O Rack Switch Number

Number 3

4

5

6

Number

3

4

5

6

01

Off (Open)

On (Closed)

On (Closed)

On (Closed)

10

On (Closed)

On (Closed)

On (Closed)

Off (Open)

02

On (Closed)

Off (Open)

On (Closed)

On (Closed)

11

Off (Open)

On (Closed)

On (Closed)

Off (Open)

03

Off (Open)

Off (Open)

On (Closed)

On (Closed)

12

On (Closed)

Off (Open)

On (Closed)

Off (Open)

PLC-5/15 processors can scan racks 01-03

13

Off (Open)

Off (Open)

On (Closed)

Off (Open)

04

On (Closed)

On (Closed)

Off (Open)

On (Closed)

14

On (Closed)

On (Closed)

Off (Open)

Off (Open)

05

Off (Open)

On (Closed)

Off (Open)

On (Closed)

15

Off (Open)

On (Closed)

Off (Open)

Off (Open)

06

On (Closed)

Off (Open)

Off (Open)

On (Closed)

16

On (Closed)

Off (Open)

Off (Open)

Off (Open)

07

Off (Open)

Off (Open)

Off (Open)

On (Closed)

17

Off (Open)

Off (Open)

Off (Open)

Off (Open)

PLC-5/25 processors can scan racks 01-07

PLC-5/40 and 5/60 processors can scan racks 01-17

Each block uses 2 words of output image table memory and 2 words of
input image table memory. Each block occupies 1/4 rack of data table, with
4 blocks comprising 1 logical rack. Image table usage for one assigned
rack number is shown in Figure 4.2 (IOBA) and Figure 4.4 (IOBB). An
example of image table usage is shown in Figure 4.3 (IOBA) and
Figure 4.5 (IOBB).

This manual is related to the following products: