Installing Block I/O
Chapter 3
3Ć5
Power Supply Requirements
An external 24V dc power supply is required to power the block. Total
current required to power the block is equal to 200mA plus an inrush of
5.5A for 10
µ
sec for each block. The supply must be able to source an
additional 100mA plus an inrush current of 400mA when a peripheral is
connected.
In addition, the external power supply should have current limiting
capabilities. The voltage range must not exceed 20.5–27.6V dc.
Wiring Requirements
Wiring cable requirements are shown in the following table.
Table 3.C
Acceptable Wiring Cables for Block I/O Connection
Use
Cable Type
With
Remote I/O Link or DIO Link
Belden 9463
PLC-2, PLC-3, PLC-5 family programmable
controllers and SLC controllers
DH-485 Data Link
Belden 9842
SLC controllers only
Input and Output wiring
Up to 14AWG
Stranded with 3/64
inch insulation
All
Figure 3.5
Remote I/O Link Wiring
Tighten screw to clamp wire.
Blue
Clear
Shield
Connection 1 2 SHD
Clear wire X
Blue wire X
Shield wire X