Rockwell Automation 1792-IB2XOB2E/B INSTL.INST ARMOR BLOCK 2 INPUT User Manual
Page 29

29
ArmorBlock 2 Input/2 Output Module
Publication 1792-5.5 – October 1996
”Enable takes effect after next powerup. Disable is required to set fixed baud rate, no
power cycle is required.”,
0,1,0,
$ Min, Max, and Default values
1,1,1,0,0,0,0,0,0;
$ Not Used
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$
Param2 =
$ Input filter Off_to_On Delay selection
0,
$ reserved
6,
$ Link Path Size
”20 0F 24 02 30 01”,
$ Link Path to param instance. The param instance
$ decodes the enumerated parameter into engineering
$ units (micro seconds).
0x0002,
$ No support for settable path, scaling, scaling links,
$ or real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported.
2,
$ Data Type – unsigned int
2,
$ Data Size – (in bytes)
”Off–to–On Delay”,
$ Parameter Name
”ms”,
$ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$
”Signal must be present for this delay period before module detects the change.”,
0,4,0,
$ Min, Max (max enumeration #), and Default values
1,1,1,0,0,0,0,0,0;
$ Not Used
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$
Param3 =
$ Input filter On_to_Off Delay selection
0,
$ reserved
6,
$ Link Path Size
”20 0F 24 03 30 01”,
$ Link Path to param instance. The param instance
decodes
$ the enumerated parameter into engineering units
$ (micro seconds).
0x0002,
$ No support for settable path, scaling, scaling links,
$ or real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported.
2,
$ Data Type – unsigned int
2,
$ Data Size – (in bytes)
”On–to–Off Delay”,
$ Parameter Name
”ms”,
$ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$
”Signal must be present for this delay period before module detects the change.”,
0,4,0,
$ Min, Max (max enumeration #), and Default values
1,1,1,0,0,0,0,0,0;
$ Not Used
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$
Param4 =
$ Fault State selection
0,
$ reserved
6,
$ Link Path Size
”20 1E 24 01 30 07”,
$ Link Path to DOG object’s fault state attribute.
0x0002,
$ No support for settable path, scaling, scaling links,
$ or real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported.
4,
$ Data Type – boolean
1,
$ Data Size
”Fault State”,
$ Parameter Name
””,
$ Units String
$$$$$$$$$$ Help string $$$$$$$$$$$