24 compactlogix ethernet/ip communication module, Certifications, Environmental specifications - 1768-enbt – Rockwell Automation 1768-ENBT CompactLogix EtherNet/IP Communication Module Installation Instructions User Manual
Page 24
![background image](/manuals/579227/24/background.png)
24 CompactLogix EtherNet/IP Communication Module
Rockwell Automation Publication 1768-IN002B-EN-P - August 2010
Surge transient immunity
• IEC 61000-4-5
±2 kV line-earth(CM) on communication ports
Conducted RF immunity
• IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from
150 kHz…80 MHz
Enclosure type rating
None (open-style)
Certifications
Certification (when
product is marked)
(1)
Value
c-UL-us
• UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584.
• UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File
E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A &
B)
C-Tick
Australian Radiocommunications Act, compliant with:
• AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres,
Protection "n"
• EN 60079-0; General Requirements
II 3 G Ex nA IIC T4
EtherNet/IP
• ODVA conformance tested to EtherNet/IP specifications
(1)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.
Environmental Specifications - 1768-ENBT
Attribute
1756-ENBT