Rockwell Automation 1768-ENBT CompactLogix EtherNet/IP Communication Module Installation Instructions User Manual
Page 23
CompactLogix EtherNet/IP Communication Module 23
Rockwell Automation Publication 1768-IN002B-EN-P - August 2010
Environmental Specifications - 1768-ENBT
Attribute
1756-ENBT
Temperature, operating
• IEC 60068-2-1 (Test Ad, Operating Cold)
• IEC 60068-2-2 (Test Bd, Operating Dry
Heat)
• IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0…60
°C (32...140 °F)
Temperature, nonoperating
• IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold)
• IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat)
• IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)
-40…85
°C (-40...185 °F)
Relative humidity
• IEC 60068-2-30 (Test Db, Unpackaged
Damp Heat)
5…95% noncondensing
Vibration
• IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10…500 Hz
Operating shock
• IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
30 g
Nonoperating shock
• IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
50 g
Emissions
• CISPR 11
Group 1, Class A
ESD immunity
• IEC 61000-4-2
4 kV contact discharges
8 kV air discharges
Radiated RF immunity
• IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%AM from
30…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at
900 MHz
10V/m with 200 Hz 50% Pulse 100%AM at
1890 MHz
1V/m with 1 kHz sine-wave 80%AM from
2000…2700 MHz
EFT/B immunity
• IEC 61000-4-4
±2 kV at 5 kHz on communication ports