Status indicators – Rockwell Automation 1768-ENBT CompactLogix EtherNet/IP Communication Module Installation Instructions User Manual
Page 21
![background image](/manuals/579227/21/background.png)
CompactLogix EtherNet/IP Communication Module 21
Rockwell Automation Publication 1768-IN002B-EN-P - August 2010
Status Indicators
The module status indicators provides the following information.
Indicator
Status
Description
NET
Off
Module is not powered, or does not have an IP
address.
• Verify there is chassis power and the module is
completely inserted into the chassis and backplane.
• Make sure the module has been configured.
Flashing Green
Module has obtained an IP address, but has no
established connections.
Green
Module has an IP address and at least one established
connection.
Flashing Red
One or more of the connections in which the module is
the target has timed out.
Red
Module has detected that its IP address is already in
use. Assign a unique IP address to the module.
Link
Off
No data transmission.
Module is not ready to communicate.
Green
Module is ready to communicate.
Flashing Green
Data transmission in progress.
Module is communicating over the network.
OK
Off
Module does not have 5V DC power. Verify there is
power and the module is properly installed.
Flashing Green
Standby mode. Module is not configured.
Green
Module is operating correctly.
Flashing Red
A minor, recoverable fault has been detected. This
could be caused by an error in the configuration.
Red
A major, unrecoverable fault has been detected.
Recycle power to the module. If this does not clear the
fault, replace the module.
Flashing Red and
Green
Module performing power-up self-test.