Specifications

ac (120V) Isolated Input Module

11

Publication 1771-IN001A–EN–P – May 2000

Inputs per Module

16

Module Location

1771-A1B thru -A4B or later I/O chassis; 1771-AM1, -AM2 chassis

Input Voltage Range

105–120V ac, 47-63Hz

Nominal Input Voltage

120V ac

Nominal Input Current

2.5mA ac

On State Voltage (minimum)

105V ac

On State Current (minimum)

2.0mA @ 105V ac

Off State Voltage (maximum)

45V ac

Off State Current (maximum)

0.8mA @ 45V ac

Input Signal Delay

Off to On
On to Off

0.57ms
Selectable: 9ms or 18.0ms

Input Impedance (minimum)

75Kohms off, 48Kohms on

Power Dissipation

7.0 Watts (max.), 0.3 Watts (min.)

Thermal Dissipation

23.8 BTU/hr (max.), 1.0 BTU/hr (min.)

Backplane Current

75mA maximum

Tested Isolation Voltage

Tested to 1500V ac channel-to-channel for 1s; 1500V ac channel to
backplane for 1s

Maximum Cable Length

1000ft (304.8m)

Environmental Conditions

Operational Temperature
Storage Temperature
Relative Humidity

0

o

to 60

o

C (32

o

to 140

o

F)

-40

o

to 85

o

C (-40

o

to 185

o

F)

5 to 95% (without condensation)

Conductors

Wire Size

Category

14 to 22 gauge (2.5mm

2

to 0.25mm

2

) stranded or solid copper only

1,2

3/64 inch (1.2mm) insulation maximum
1

3

Keying

Between 22 and 24
Between 26 and 28

Wiring Arm

Catalog Number 1771-WN

Wiring Arm Screw Torque

9 pound-inches (1.0Nm)

Agency Certification
(when product is marked)

CSA certified

CSA Class 1, Division 2, Groups A, B, C and D certified

UL listed

CE marked for all applicable directives

C-Tick marked for all applicable acts

1

One or two 14–22 AWG solid or stranded copper wires per terminal. Must be same size. Do not intermix solid and stranded wires. Use copper

wire only.

2

14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller wire size may be required.

3

Refer to publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.”