Plc-5 family processors – Rockwell Automation 1771-IR Series D RTD Input Module User Manual User Manual
Page 55
Programming Examples
B–3
Publication 1771Ć6.5.129 - March 2000
1. Press [SHIFT][MODE] to display your ladder diagram on the
industrial terminal.
2. Press DD,03:0[ENTER] to display the block transfer write file.
The industrial terminal screen should look like Figure B.2. Notice
the highlighted block of zeroes. This highlighted block is the cursor.
It should be in the same place as it appears in figure B.2. If it is not,
you can move it to the desired position with the cursor control keys.
Once you have the highlighted cursor in the right place, you can go
on to step 3.
Figure B.2
Write Block Transfer for a PLC-3 Processor
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000000 00000000
00000
00004
00010
00014
00020
WORD #
0
1
2
3
START - W0003 : 0000
DATA MONITOR
PROG : I/O OFF
NO FORCES :
NO EDITS :
RUNG # [RM000000]
: MEM PROT OFF
$ W03:0 - [ ]
3. Enter the data corresponding to your bit selection in word 0.
4. When you have entered your data, press [ENTER]. If you make a
mistake, make sure the cursor is over the word you desire to
change. Enter the correct data and press [ENTER].
5. Press [CANCEL COMMAND]. This returns you to the ladder
diagram.
The following is a sample procedure for entering data in the
configuration words of the block transfer write instruction when
using a PLC–5 processor. For a complete sample program, refer to
Figure 4.3.
1. Enter the following rung:
EN
BTW
BLOCK XFER WRITE
RACK:
GROUP:
MODULE:
CONTROL:
0
0
0
N7:0
DN
DATA FILE:
LENGTH:
CONTINUOUS:
N7:60
14
N
ER
Power Up Bit
N7:60 is the address of the BTW transfer file.
PLC-5 Family Processors