24 CompactLogix Controllers
Publication
1768-IN004D-EN-P - December 2009
OK
Off
No power is applied. If MEM SAVE indicator is green,
the user program and configuration data are being
saved to flash memory.
Flashing red
•
The controller requires a firmware update or a
firmware update is in progress.
•
A recoverable major fault occurred on the
controller.
•
A nonrecoverable major fault occurred on the
controller.
•
See
Clear a Major Fault on page 26
Red
The controller detected a nonrecoverable major fault so
it cleared the project from memory.
See
Clear a Nonrecoverable Fault on page 27
.
Green
Controller is OK.
Flashing green
The controller is storing or loading a project to or from
nonvolatile memory.
CF
Off
There is no CompactFlash card activity.
Flashing green
The controller is reading from or writing to the
CompactFlash card.
IMPORTANT: Do not remove the CompactFlash card
while the controller is reading from or writing to the
card. Removing the card during a read or write could
corrupt data on the card, data in the controller, and
firmware installed on the controller.
Flashing red
The CompactFlash card does not have a valid file
system and must be replaced.
DCH0
Off
Channel 0 is configured differently than the default
serial configuration.
Green
Channel 0 has the default serial configuration.
CH0
Off
No RS-232 activity.
Green
RS-232 activity.
Controller Status Indicators
Indicator
State
Description