Publication 1405-IN002C-EN-P - November 2004

Bulletin 1405 (M620) Operating Instructions 13

Notes:

Registers 0 to 35 contain the named measured values.

Registers 18 to 39 represent values as 32 bit DWORD.

Registers are organized as “big-Endian”, with first the high-Byte
and then the low-Byte. The transferred bytes are not in a rising
sequence, but the higher register follows after the lower register.

Register 40 returns the status of device M620 and status
over/under voltage alarm.

Register 41 returns the node address and baud rate.

Registers 42 to 49 return diagnostic registers per the Modbus
specifications.

Registers 80 and 81 are read/write registers for over/under
voltage parameter.

Register 82 is a read/write register for control of M620 functions:
reset I peak, reset E-Counter.

34

68

E3 real energy

DWORD

35

70

36

72

Total Power

DWORD

37

74

38

76

Total Energy

DWORD

39

78

40

80

Status/Alarm

WORD

41

82

Baud/Address

WORD

42

84

Diagnostic 0

WORD

43

86

Diagnostic 1

WORD

44

88

Diagnostic 2

WORD

45

90

Diagnostic 3

WORD

46

92

Diagnostic 4

WORD

47

94

Diagnostic 5

WORD

48

96

Diagnostic 6

WORD

49

98

Diagnostic 7

WORD

80

100

Under Voltage

WORD

81

102

Over Voltage

WORD

82

104

Control

WORD

Table 6 Modbus Memory Map

Register

Byte Low

Metered Value

Data Type