Rockwell Automation 1609 Industrial Uninterruptible Power Supply - Series D User Manual
Page 3

1. To access the battery compartment remove the six screws and the battery door.
2. Remove the battery container, jumpers and wire harness from the battery compartment. Place the battery
container and batteries onto a flat surface. Use the provided jumper wires to connect the batteries in
series. Connect the positive terminal (red) of the battery to the negative terminal (black) of another battery.
See photo below for details.
3. Connect the shorter set of red and black wires of the harness to the top terminals(red – to – red and black –
to – black). Connect the longer set of red and black wires of the harness to the bottom terminals (red – to –
red and black – to – black) and route the wires through the cut-out hole. See photo below for details.
4. Fold the battery container and seal it with tape.
1609-EXBAT Batteries Wiring and Installation Instruction Only
Only use battery wires that have been provided with the 1609-EXBAT.
Warning: A disconnect switch shall be provided by others for DC output circuit. To reduce the risk of fire, connect only to a circuit
provided with branch circuit overcurrent protection for 35 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70“
Before connecting a battery pack to UPS, the emergent disconnecting device shall be provided between the UPS and battery pack.
Bulletin 1609 Industrial Uninterruptible Power Supply
3
Publication 1609-IN012B-EN-P - August 2012 DIR 10000234085 (Version 01)
Red
Red
Red
Red
Black
Black
Red
Black
Black
Black
Red
Black
Top
Red
Bottom
Red
Top
Black
Bottom
Black
Cut-Out
Hole