EN921 - Variable Voltage w/ PI Power/Current Control

7

The following parameter(s) have been modified to provide special functionality required by the
application (changes indicated in bold):

Voltage PI

[Pwr / Cur Ref Lo]

Sets the percentage of power or current reference that
represents the low end of the “Range”.

Parameter Number

342

Parameter Type

Read/Write

Display Units / Drive Units

0.1% / 4096 = 100%

Factory Default

0.0%

Minimum Value

–300.0%

Maximum Value

+300.0%

[Pwr / Cur Ref Hi]

Sets the percentage of power or current reference that
represents the high end of the “Range”.

Parameter Number

343

Parameter Type

Read/Write

Display Units / Drive Units

0.1% / 4096 = 100%

Factory Default

100.0%

Minimum Value

–300.0%

Maximum Value

+300.0%

[PWM Frequency]

This parameter sets the carrier frequency for the sine cod-
ed PWM output waveform.

This parameter cannot be changed while the drive is running.

Refer to the Derating Guidelines in Appendix A.

Parameter Number

45

Parameter Type

Read and Write

Display Units / Drive Units

2 KHz / KHz/2

Factory Default

2 KHz

Minimum Value

1 KHz

Maximum Value

A & B Frame Drives = 8 kHz

C Frame Drives & Up = 6 kHz

[VT Scaling]

This parameter scales the drive for VT ampere ratings.

Important: This parameter must be set to “Disabled” when
drive is used in a fibers application.

This parameter cannot be changed while the drive is
running.

Parameter Number

203

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

Disables Variable Torque Scaling

“Enabled” 1

Enables Variable Torque Scaling

[Load Loss Level]

Sets the torque current level below which a load loss fault/
warning will occur. The value is expressed as a
percentage of programmed [Motor NP Amps].

Parameter Number

291

Parameter Type

Read and Write

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

50%

Minimum Value

5%

Maximum Value

100%