EN921 - Variable Voltage w/ PI Power/Current Control

3

Voltage Control

[Volt Trim%]

This parameter specifies the voltage trim percentage add-
ed/deducted from the [Voltage Command] reference. The
value represents

±

Volt Trim% of drive [Rated Voltage].

Minimum Input = –Volt Trim% Value
Mid-Point Input = No Trim
Maximum Input = +Volt Trim% Value

The volt trim signal can be “inverted” by entering a negative
value.

Parameter Number

340

Parameter Type

Read and Write

Display Units / Drive Units

1% / 4096 = 100%

Factory Default

0%

Minimum Value

-100%

Maximum Value

+100%

[Volt Command Ref]

This parameter specifies the drive output voltage when
[Volt Select] is set to “Volt Cmd Ref”. The parameter value
is cleared at power-up and is not retained in EEPROM
storage. This parameter can be be “linked” with a
SCANport communications adapter via the [Data In xx]
Adapter I/O parameters.

Parameter Number(s)

341

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rated Volts

Factory Default

0 Volts

Minimum Value

0 Volts

Maximum Value

120% Drive Rated Volts