Pi feedback, Pi error, Pi output – Rockwell Automation 1336F PLUS II Custom Firmware Instructions - EN921 User Manual
Page 6: Ki process, Kp process, Pi neg limit, Pi pos limit, Pi preload, Voltage pi
6
EN921 - Variable Voltage w/ PI Power/Current Control
[PI Feedback]
This parameter displays the current value of the reference
selected by [PI Fdbk Select].
Parameter Number
218
Parameter Type
Read Only
Display Units / Drive Units
None / 4096 = 100%
Factory Default
None
Minimum Value
–4915
Maximum Value
4915
[PI Error]
The value of the error calculated by the PI loop. This value
is the difference between [PI Reference] & [PI Feedback]
and determines the PI output.
Parameter Number
219
Parameter Type
Read Only
Display Units / Drive Units
None / 4096 = 100%
Factory Default
None
Minimum Value
–4915
Maximum Value
4915
[PI Output]
The current output of the PI loop is displayed with this
parameter. This output is used as the reference for the
voltage output.
Parameter Number
220
Parameter Type
Read Only
Display Units / Drive Units
1 Volt / 4096 = Drive Rated Volts
Factory Default
None
Minimum Value
–120% Rated Voltage
Maximum Value
120% Rated Voltage
[KI Process]
This parameter sets the integral gain of the process PI
loop.
Parameter Number
221
Parameter Type
Read/Write
Display Units / Drive Units
NA / NA
Factory Default
128
Minimum Value
0
Maximum Value
2048
[KP Process]
This parameter sets the proportional gain of the process
PI loop.
Parameter Number
222
Parameter Type
Read/Write
Display Units / Drive Units
NA / NA
Factory Default
256
Minimum Value
0
Maximum Value
2048
[PI Neg Limit]
This parameter sets the lower (negative) limit of the PI
output.
Parameter Number
223
Parameter Type
Read/Write
Display Units / Drive Units
None / 4096 = 100%
Factory Default
-341
Minimum Value
–4915
Maximum Value
4915
[PI Pos Limit]
This parameter sets the upper (positive) limit of the PI
output.
Parameter Number
224
Parameter Type
Read/Write
Display Units / Drive Units
None / 4096 = 100%
Factory Default
341
Minimum Value
–4915
Maximum Value
4915
[PI Preload]
Sets the value used to preload the PI integrator when “Set
Output” or “Preload Int” bits equal “1” in [PI Config].
Parameter Number
225
Parameter Type
Read/Write
Display Units / Drive Units
None / 4096 = 100%
Factory Default
0
Minimum Value
–4915
Maximum Value
4915