VIII. Appendix A - 800 Housing to 1756 Chassis Conversion System Selection Process

1) Determine the number of 800 I/O modules actually used in the 800 I/O Housing to be converted to 1756 I/O .
2) Review the data in Column 5 from the below table, and select a 1756 I/O Chassis which meets your conversion

needs from Step 1. Ensure the information from the I/O Conversion module table is reviewed first since in some
cases, two 1756 modules are needed to replace one 800 I/O module.

3) Once the 1756 Chassis is selected, refer to Column 7 and select the Conversion Assembly.

One chassis slot required for the ControlLogix processor or a remote I/O adapter type module.

The footprint and mounting dimensions of the 1492 Conversion Assembly (base-plate and cover-plate) match those of the

Modicon I/O Housing.

Width dimension includes the 1756 Chassis power supply.

Surplus Chassis width as compared to the 800 I/O Housing is divided equally when mounting it on the Conversion Assembly.

Mounting holes for the 1756 I/O Chassis are pre-drilled and pre-tapped into the Conversion Assembly cover-plate.

Modicon is a Registered Trademark of Group Schneider.

AS-H810-xxx

AS-H819-103

AS-H819-209

AS-H819-100

AS-H827-103

AS-H827-209

AS-B827-100

Modicon 800 I/O

Housing Cat Number

1492-MUA4-MB3

1492-MUA7-A10-

MB4679 

1492-MUA10-A13-

MB81011 

Conversion Assembly

Catalog Number

Max. Number

of 800 Housing

Slots for I/O

3

4

6

7

8

10

11

10.25”

17.5”

17.5”

17.5”

27.1”

27.1”

27.1”

800 Housing

Width

Dimension

10.25”

A7 = 14.49”

A10 = 19.02”

A7 = 14.49”

A10 = 19.02”

A7 = 14.49”

A10 = 19.02”
A10 = 19.02”

A13 = 23.15”
A10 = 19.02”

A13 = 23.15”
A10 = 19.02”

A13 = 23.15”

1756 Chassis

Width 

Dimension

Max. Number

of 1756 Chassis

Slots for I/O

3

A7 = 6, A10=9

A7 = 6, A10=9

A7 = 6, A10=9

A10 = 9, A13=12

A10 = 9, A13=12

A10 = 9, A13=12

1756 I/O Chassis

Catalog Number

1

7

2

3

6

5

4

1756-A4

1756-A7

or

1756-A10

1756-A10

or

1756-A13

BUL. 592 E1 PLUS O.L. RELAY
APPLICATION AND INSTALLATION
INSTRUCTION SHEET

10000015209 00

- - - - - - - - -

- - - - - - - - -

4

4

B

Conversion Module

Compatible 800

Output Module

Compatible 1756

Module

Required 1492 Cable

1492-CM800-LD006

B820-008

1756-OB8

1492-CABLEU

1492-CM800-LD006

B820-008

1756-OC8

1492-CABLEU

1492-CM800-LD006 Conversion Module

20-Pin Connector for 1492-CABLEU

Mating Connector for
B800 Terminal Block

De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out
to any device in the control cabinet where the conversion is to be performed. Ensure work is
performed by qualified personnel.

WARNING