Rockwell Automation 1609-S350NS_ES Uninterruptible Power Supply - 350VA User Manual
Page 8
9
User Configurable Items
Synchronized
Turn-on Delay
0 seconds
• 0 s
• 60 s
• 120 s
• 180 s
• 240 s
• 300 s
• 360 s
• 420 s
Specify the time the UPS will wait after the
return of utility power before start-up (to avoid
branch circuit overload).
High Transfer Point
120 V models:
127 VAC
230 V models:
253 VAC
• 127 VAC
• 130 VAC
• 253 VAC
• 257 VAC
• 133 VAC
• 136 VAC
• 261 VAC
• 265 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically high, set the high
transfer point higher if the connected
equipment can tolerate this condition.
Low Transfer Point
120 V models:
106 VAC
230 V models:
208 VAC
• 97 VAC
• 100 VAC
• 196 VAC
• 200 VAC
• 103 VAC
• 106 VAC
• 204 VAC
• 208 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low
transfer point lower if the connected equipment
can tolerate this condition.
The 1609-S350ES ships ready for 230 V
sources. When operating the UPS in 208 V
applications, the UPS low transfer voltage
settings are adjusted through PowerChute
software. The proper setting for low transfer
voltage is 196 V.
Refer to the PowerChute user guide for setting
adjustment details.
Output Voltage
230 V models only
230 VAC
• 220 VAC
• 230 VAC
• 240 VAC
Sets the output voltage of the UPS while
operating on battery.
Function
Factory Default
User Selectable Choices
Description