Rockwell Automation 1608P ProDySC Installation Instructions, 25 and 50 A User Manual
Page 13

Rockwell Automation Publication 1608P-IN001B-EN-P - May 2014
13
Installation
Chapter 2
Table 2 - ProDySC 25 Amp Power Cable Terminations
Table 3 - ProDySC 50Amp Power Cable Terminations
3 Wire with a Ground
Terminal
Connection
Function
Terminal Marking
Wire Range
AWG (mm2)
Torque lb-in
(Nm)
AC Input
Phase A, B, C
L1, L2, L3
24- 8 (0.5-6)
7.1- 8.9
(0.8-1)
Ground
¼-20 Stud
65
(7.3)
AC Output
Phase A, B, C
X1, X2, X3
24-8 (0.5-6)
7.1- 8.9
(0.8-1)
Ground
¼-20 Stud
65
(7.3)
4 Wire with a Ground
AC Input
Phase A, B, C
L1, L2, L3
24- 8 (0.5-6)
7.1- 8.9
(0.8-1)
Ground
¼-20 Stud
65
(7.3)
Neutral
N
10-0 (6-50)
24.9- 26.7
(2.8-3)
AC Output
Phase A, B, C
X1, X2, X3
24- 8 (0.5-6)
7.1- 8.9
(0.8-1)
Neutral
N
10-0 (6-50)
24.9- 26.7
(2.8-3)
Ground
¼-20 Stud
65
(7.3)
3 Wire with a Ground
Terminal
Connection
Function
Terminal Marking
Wire Range
AWG (mm2)
Torque lb-in
(Nm)
AC Input
Phase A, B, C
L1, L2, L3
10-0 (6-50)
24.9-26.7
(2.8-3)
Ground
¼-20 Stud
65 (7.3)
AC Output
Phase A, B, C,
X1, X2, X3
10-0 (6-50)
24.9-26.7
(2.8-3)
Ground
¼-20 Stud
65 (7.3)
4 Wire with a Ground
AC Input
Phase A, B, C
and Neutral
L1, L2, L3, N
10-0 (6-50)
24.9-26.7
(2.8-3)
Ground
¼-20 Stud
65 (7.3)
AC Output
Phase A, B, C
and Neutral
X1, X2, X3, N
10-0 (6-50)
24.9-26.7
(2.8-3)
Ground
¼-20 Stud
65 (7.3)
WARNING: The ProDySC must be safety-grounded according to the National
Code. In addition, all local, state, and federal regulations applicable to the
installation of electrical systems as well as accident prevention regulations
must be strictly observed.