Operating diagram, Active and ready signals, inhibit input – Rockwell Automation 1606-XLSBUFFER48 Power Supply Reference Manual User Manual
Page 7
All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM027A-EN-P — April 2014
7
Bulletin 1606 Switched Mode Power Supplies
10. Operating Diagram
Fig. 10-1 Operating diagram
Fig. 10-2 Signals schematic
Ready
t
Active
t
Optocoupler high ohmic
Optocoupler high ohmic
Optocoupler low ohmic
Optocoupler
low ohmic
V
Mains
t
V
Buffer
Capacitor
t
V
out
t
Charging Mode
LED
t
Buffer Mode
Hold-up Time Power Supply
Standby
Mode
10Hz
1.25Hz
8 Ready
7 Active
6 +
5,1V
3mA
9 Inhibit
11. Active and Ready Signals, Inhibit Input
Active signal (Pin 7)
low ohmic while buffer capacitors are discharging
Signal
voltage
max.
60Vdc
Signal
current
max.
6mA
Voltage drop across opto-coupler
typ
1.2V / 3.3V
at 1mA / 5mA, while opto-coupler is low ohmic
Leakage
current
max.
50μA
while opto-coupler is high ohmic
Isolation
nom.
500Vac
signal port to power port
Ready signal (Pin 8)
low ohmic when buffer is fully charged
Signal
voltage
max.
60Vdc
Signal
current
max.
6mA
Voltage drop across opto-coupler
typ
1.2V / 3.3V
at 1mA / 5mA, while opto-coupler is low ohmic
Leakage
current
max.
50μA
while opto-coupler is high ohmic
Isolation
nom. 500Vac
signal
port
to
power
port
Inhibit input (Pin 9)
“High” input signal initiates unit shutdown and buffer discharge
Signal
voltage
max.
60Vdc
Signal
current
max.
4mA
current
limited
Shut-down threshold
min.
6Vdc
unit is in shut-down mode above this threshold level.
max.
10Vdc
Isolation
nom. 500Vac
signal
port
to
power
port
Wiring diagrams can be found in section 20.