beautypg.com

Operating diagram, Active and ready signals, inhibit input – Rockwell Automation 1606-XLSBUFFER48 Power Supply Reference Manual User Manual

Page 7

background image

All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM027A-EN-P — April 2014

7

Bulletin 1606 Switched Mode Power Supplies

10. Operating Diagram

Fig. 10-1 Operating diagram

Fig. 10-2 Signals schematic

Ready

t

Active

t

Optocoupler high ohmic

Optocoupler high ohmic

Optocoupler low ohmic

Optocoupler

low ohmic

V

Mains

t

V

Buffer

Capacitor

t

V

out

t

Charging Mode

LED

t

Buffer Mode

Hold-up Time Power Supply

Standby

Mode

10Hz

1.25Hz

8 Ready

7 Active

6 +

5,1V

3mA

9 Inhibit

11. Active and Ready Signals, Inhibit Input

Active signal (Pin 7)

low ohmic while buffer capacitors are discharging

Signal

voltage

max.

60Vdc

Signal

current

max.

6mA

Voltage drop across opto-coupler

typ

1.2V / 3.3V

at 1mA / 5mA, while opto-coupler is low ohmic

Leakage

current

max.

50μA

while opto-coupler is high ohmic

Isolation

nom.

500Vac

signal port to power port

Ready signal (Pin 8)

low ohmic when buffer is fully charged

Signal

voltage

max.

60Vdc

Signal

current

max.

6mA

Voltage drop across opto-coupler

typ

1.2V / 3.3V

at 1mA / 5mA, while opto-coupler is low ohmic

Leakage

current

max.

50μA

while opto-coupler is high ohmic

Isolation

nom. 500Vac

signal

port

to

power

port

Inhibit input (Pin 9)

“High” input signal initiates unit shutdown and buffer discharge

Signal

voltage

max.

60Vdc

Signal

current

max.

4mA

current

limited

Shut-down threshold

min.

6Vdc

unit is in shut-down mode above this threshold level.

max.

10Vdc

Isolation

nom. 500Vac

signal

port

to

power

port

Wiring diagrams can be found in section 20.