All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM027A-EN-P — April 2014

5

Bulletin 1606 Switched Mode Power Supplies

7. Buffer Mode

Rated output current

nom.

20A

Current limitation

min.

20A

Electronically limited

Output voltage

typ.

45V

Jumper in position “45V fixed”

typ.

2V below input
voltage

Jumper in position “Vin –2V”

Ripple and noise voltage

max.
max. 400mVpp 10A, 20 Hz to 20 MHz, 50Ohm
max. 600mVpp 20A, 20Hz to 20MHz, 50Ohm
may increase below -10°C

250mVpp 5A,

20Hz

to

20MHz,

50Ohm

Hold-up time

min.

0.1s

45V, 20A

typ. 0.15s

45V,

20A

min. 13.4s

45V,

0.1A

typ. 21s

45V,

0.1A

To increase buffer current or extend hold-up time, any given number of buffer
units can be installed in parallel.

Activation threshold

typ.

45V

Ju

mper in position “45V fixed”

Buffering starts if terminal voltage falls below 22.5V.

typ.

Vin –2V

Jumper in position “Vin –2V”
Buffering starts if the terminal voltage decreases by
more than 2V. Buffering ends when terminal voltage
increases by more than 2V.
Voltage changes slower than 1.1V/s will be ignored
unless the voltage is above 45V. Below 45V
buffering starts immediately.

Status lamp

flashes 10Hz

Active signal

low ohmic

Ready signal

high ohmic


Fig. 7-1 Hold-up time

0,01 A

0,10 A

1,00 A

10,00 A

100,00 A

0,1 s

1,0 s

10,0 s

100,0 s

Buffer

Current

typ. ( 45,0 V )

typ. ( 56,0 V )

min. ( 45 V )