Buffer mode – Rockwell Automation 1606-XLSBUFFER48 Power Supply Reference Manual User Manual
Page 5
All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM027A-EN-P — April 2014
5
Bulletin 1606 Switched Mode Power Supplies
7. Buffer Mode
Rated output current
nom.
20A
Current limitation
min.
20A
Electronically limited
Output voltage
typ.
45V
Jumper in position “45V fixed”
typ.
2V below input
voltage
Jumper in position “Vin –2V”
Ripple and noise voltage
max.
max. 400mVpp 10A, 20 Hz to 20 MHz, 50Ohm
max. 600mVpp 20A, 20Hz to 20MHz, 50Ohm
may increase below -10°C
250mVpp 5A,
20Hz
to
20MHz,
50Ohm
Hold-up time
min.
0.1s
45V, 20A
typ. 0.15s
45V,
20A
min. 13.4s
45V,
0.1A
typ. 21s
45V,
0.1A
To increase buffer current or extend hold-up time, any given number of buffer
units can be installed in parallel.
Activation threshold
typ.
45V
Ju
mper in position “45V fixed”
Buffering starts if terminal voltage falls below 22.5V.
typ.
Vin –2V
Jumper in position “Vin –2V”
Buffering starts if the terminal voltage decreases by
more than 2V. Buffering ends when terminal voltage
increases by more than 2V.
Voltage changes slower than 1.1V/s will be ignored
unless the voltage is above 45V. Below 45V
buffering starts immediately.
Status lamp
flashes 10Hz
Active signal
low ohmic
Ready signal
high ohmic
Fig. 7-1 Hold-up time
0,01 A
0,10 A
1,00 A
10,00 A
100,00 A
0,1 s
1,0 s
10,0 s
100,0 s
Buffer
Current
typ. ( 45,0 V )
typ. ( 56,0 V )
min. ( 45 V )