All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

2

Rockwell Automation Publication 1606-RM027A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

Buffer Unit

Buffering with electrolytic capacitors instead

of lead batteries

Buffering of 48V loads

Minimum hold-up time 0.1s at 20A and 0.2s at 10A

Longer hold-up time at lower loads

Clear status indication by status LED and signaling

terminals

Quick-connect spring-clamp terminals

3 year warranty

1. Description

2. Specification Quick Reference

Rated voltage

DC 48V

Voltage range

48-56V

Output voltage

45V or
V

IN

–2V

Buffer mode
select with jumper

Output current

0 to 20A

Hold-up time

min 0.1s

45V, 20A

typ 0.15s

45V, 20A

min 13.4s

45V, 0.1A

typ 21s

45V, 0.1A

Charging current

max 500mA

Charging time

typ 21s

Input current

typ 40mA

standby mode

Power dissipation

typ 1.9W

standby mode

Temperature range

-25°C to +70°C

operational

Dimensions 64x124x102mm

WxHxD

The buffer unit is a supplementary device for regulated
DC48V power supplies. It buffers load currents during
typical mains faults and load peaks.

Working principle
In times when the power
supply provides sufficient
voltages, the buffer unit
stores energy in integrated electrolytic capacitors. In case of
mains voltage fault, this energy is released again in a
regulated process.

Bridges mains faults
without interruption
Statistic show that 80% of
all mains fault lasts less
than 0.2s. These mains
faults are completely bridged by the buffer unit. This
increases the reliability of the system as a whole.

Extended hold-up time
Once mains power fails or
is switched off, the buffer
unit will continue to
provide the load current
for a defined period of time. Process data can be saved and
processes can be terminated before the DC power switches
off. Controlled restarts are subsequently possible.

Easy to handle, expandable and maintanance-free
The buffer unit does not require
any control wiring. It can be
added parallel to the load circuit
at any given point. Buffer units
can be switched in parallel to
increase the output ampacity or the hold-up time.

DC

Charge

Discharge

Buffer

AC

DC

Buffer Unit

AC

DC

Buffer Unit

DC

Buffer

Unit(s)

Power

Supply

Load

AC

+

-