Mounting orientations – Rockwell Automation 1606-XLE96B-2 Power Supply Reference Manual User Manual
Page 21
All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM030A-EN-P — April 2014
21
Bulletin 1606 Switched Mode Power Supplies
22.11. Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximal allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1
Recommended output current.
Curve A2
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 22-5
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Output Current
0
10
20
30
40
60°C
2
4
6
8A
50
A1
Ambient Temperature
Fig. 22-6
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPU
T
Output Current
0
10
20
30
40
60°C
2
4
6
8A
50
Ambient Temperature
A2
A1
Fig. 22-7
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10
20
30
40
60°C
2
4
6
8A
50
Ambient Temperature
A1
A2
Fig. 22-8
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
IN
PU
T
Output Current
0
10
20
30
40
60°C
2
4
6
8A
50
Ambient Temperature
A1
A2
Fig. 22-9
Mounting
Orientation E
(Horizontal ccw)
Power Supply
OUTPUT
IN
PU
T
Output Current
0
10
20
30
40
60°C
2
4
6
8A
50
Ambient Temperature
A1
A2