beautypg.com

Protection features, Safety features, Dielectric strength – Rockwell Automation 1606-XLE96B-2 Power Supply Reference Manual User Manual

Page 13

background image

All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM030A-EN-P — April 2014

13

Bulletin 1606 Switched Mode Power Supplies

15. Protection Features

Output protection

Electronically protected against overload, no-load and short-circuits

*)

Output over-voltage protection

typ. 18Vdc
max. 20Vdc

In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.

Degree of protection

IP 20

EN/IEC 60529

Penetration protection

> 3.5mm

e.g. screws, small parts

Over-temperature protection

yes

output shut-down with automatic restart

Input transient protection

MOV (Metal Oxide Varistor) and active transient filter

Internal input fuse

2x T3.15A H.B.C.

not user replaceable

*) In case of a protection event, audible noise may occur.


16. Safety Features

Input / output separation

*)

SELV

IEC/EN

60950-1

PELV

IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41

Class of protection

I

PE (Protective Earth) connection required

Isolation resistance

> 5MOhm

input to output, 500Vdc

PE resistance

< 0.1Ohm

Touch current (leakage current)

typ. 0.14mA

400Vac, 50Hz, TN mains

typ. 0.19mA

480Vac, 60Hz, TN mains

< 0.18mA

440Vac, 50Hz, TN mains

< 0.25mA

528Vac, 60Hz, TN mains

*) Double or reinforced insulation


17. Dielectric Strength

The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.

Fig. 17-1 Dielectric strength

A B C

Type test

60s

2500Vac

3000Vac 500Vac

Factory test

5s

2500Vac 2500Vac 500Vac

Field test

5s

2000Vac

2000Vac

500Vac

Cut-off current setting

> 5mA

> 5mA

> 15mA

A

C

B

L1

Input

Earth

Output

-

+

L2


To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit be connected to the protective earth system.
This prevents situations in which a load starts unexpectedly or
cannot be switched off in the occurence of unnoticed earth faults.