Protection features, Safety features, Dielectric strength – Rockwell Automation 1606-XLE96B-2 Power Supply Reference Manual User Manual
Page 13
All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM030A-EN-P — April 2014
13
Bulletin 1606 Switched Mode Power Supplies
15. Protection Features
Output protection
Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection
typ. 18Vdc
max. 20Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 3.5mm
e.g. screws, small parts
Over-temperature protection
yes
output shut-down with automatic restart
Input transient protection
MOV (Metal Oxide Varistor) and active transient filter
Internal input fuse
2x T3.15A H.B.C.
not user replaceable
*) In case of a protection event, audible noise may occur.
16. Safety Features
Input / output separation
*)
SELV
IEC/EN
60950-1
PELV
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 5MOhm
input to output, 500Vdc
PE resistance
< 0.1Ohm
Touch current (leakage current)
typ. 0.14mA
400Vac, 50Hz, TN mains
typ. 0.19mA
480Vac, 60Hz, TN mains
< 0.18mA
440Vac, 50Hz, TN mains
< 0.25mA
528Vac, 60Hz, TN mains
*) Double or reinforced insulation
17. Dielectric Strength
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 17-1 Dielectric strength
A B C
Type test
60s
2500Vac
3000Vac 500Vac
Factory test
5s
2500Vac 2500Vac 500Vac
Field test
5s
2000Vac
2000Vac
500Vac
Cut-off current setting
> 5mA
> 5mA
> 15mA
A
C
B
L1
Input
Earth
Output
-
+
L2
To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit be connected to the protective earth system.
This prevents situations in which a load starts unexpectedly or
cannot be switched off in the occurence of unnoticed earth faults.