Mounting operations – Rockwell Automation 1606-XLP15A Power Supply Reference Manual User Manual
Page 22

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
22
Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
20.11. Mounting Operations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the max. allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 20-5
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Output Power
0
10
20
30
40
60°C
3
9
12
15W
50
A1
6
Ambient Temperature
Fig. 20-6
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPU
T
Output Power
0
10
20
30
40
60°C
3
9
12
15W
50
6
A1
A2
Ambient Temperature
Fig. 20-7
Mounting
Orientation C
(Table-top
mounting)
Output Power
0
10
20
30
40
60°C
3
9
12
15W
50
6
A1
A2
Ambient Temperature
Fig. 20-8
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
IN
PU
T
Output Power
0
10
20
30
40
60°C
3
9
12
15W
50
6
A1
A2
Ambient Temperature
Fig. 20-9
Mounting
Orientation E
(Horizontal ccw)
Pow
er
Supp
ly
OUTP
UT
IN
PUT
Output Power
0
10
20
30
40
60°C
3
9
12
15W
50
6
A1
A2
Ambient Temperature