Rockwell Automation 1492- 1771-N Series I/O to 1756 ControlLogix I/O User Manual
Page 7
V. Wiring Diagrams (Continued)
Conversion: 1771-NIS (1) To 1756-IF6CIS (2) (Current)
Using Existing 1771-RTP4 Interface Module
(7)
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
WARNING
Cable “B”
1492-CONACAB020N2
Cable “A”
1492-CONACAB020N2
Interface Module
1771-RTP4
1756-IF6CIS
1756-IF6CIS
B1
B2
B3
B4
B5
A4
A5
B8
B9
A6
A7
B12
B13
A8
A9
B16
B17
A10
A11
W2
SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
CURRENT
LOAD
A1
A2
A3
B12
B13
A12
A13
B14
B15
A14
A15
B16
B17
A16
A17
B18
B19
A18
A19
CR
W1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
15
16
18
19
21
22
24
5
3
4
6
11
9
10
12
Black
Brown
Green
Yellow
White/Black
White/Red
Violet
Red
I-OUT-0
I-OUT-1
I-OUT-2
I-OUT-3
I-RTN-0
I-RTN-2
I-RTN-3
N/A
N/A
N/A
25
N/A
N/A
N/A
-
I-RTN-1
CURRENT
LOAD
+
-
24VDC
SUPPLY
24VDC
SUPPLY
+
5
3
4
6
11
9
10
12
I-OUT-0
I-OUT-1
I-OUT-2
I-OUT-3
I-RTN-0
I-RTN-2
I-RTN-3
I-RTN-1
Black
Brown
Green
Yellow
White/Black
White/Red
Violet
Red
15
16
18
19
21
22
24
25
PN-107134
DIR 10000165561 (Version 01)
Publication 1492-IN104B-EN-E
Conversion Module Installation and Application Considerations
Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-IF6CIS.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-073 (Version 00)]