2

1397 Regulated Field Supply Card

1397 – 5.17 September, 1997

ABS

SOFTWARE
SCALING

A/D

FIELD

CURRENT

FEEDBACK

100

P.274
[Fld Econ Ref]

P.044
[Motor Field Amps]

P.281
[Fld Loop K-Fdbk]

P.044
[Motor Field Amps]

P.044
[Motor Field Amps]

P. 280
[Field Reference]

MUL DIV

GAIN

LO

0

HI

GAIN

MUL

ON

OFF

P.176
[Field Ref TP]

P.279

[Fld Loop Kp]

P.175
[Fld Econ Active]

DISABLED

ENABLED

WLD

KP

HI

PI Block 2

LO

1 P.275 [Fld Auto Weak] is clamped to Disabled when

P.039 [Feedback Type] = P.005 [Armature Voltage].

0

°

+

LO

HI

PI Block 1

KP

WLD

FIELD PHASE
FIRING LOGIC

FIELD
REGULATOR
SUPPLY

P.276
[Fld Delta Hi Lim]

P.275

1

[Fld Auto Weak]

P.010
[Field Feedback]

P.174
[Field Delta]

P.284
[Field Weaken Level]

P.045
[Motor Arm Amps]

P.066
[IR Compensation]

P.282
[Fld Weak Ld Freq]

P.283
[Field Weaken KP]

P.006
[Cur Loop Fdbk]

(8-Sample Average)

P.066
[IR Compensation]

SOFTWARE
SCALING

SOFTWARE
SCALING

+

+

+

P.278
[Fld Lp Lead Freq]

Field Current Regulator

Armature Voltage Regulator

ARMATURE

VOLTAGE

P.276
[Field Delta Hi Lim]

How This Option Works

Field Control Loop Parameters

P.044 [Motor Field Amps]

P.277 [Fld Loss Level]

P.045 [Motor Arm Amps]

P.278 [Fld Lp Lead Freq]

P.066 [IR Compensation]

P.279 [Fld Loop Kp]

P.273 [Fld Econ Delay]

P.280 [Field Reference]

P.274 [Fld Econ Ref]

P.281 [Fld Loop K-Fdbk]

P.275 [Fld Auto Weak]

P.283 [Fld Weaken Kp]

P.276 [Fld Delta Hi Lim]

P.284 [Fld Weaken Level]

For the drive to operate, one of the following field supply
options must be present.

A Fixed Field Supply

A Regulated Field Supply

An Enhanced Field Supply

At power-up if the Regulated Field Supply Card is installed:

1.

P.177 [Field Regulator]

will detect it’s presence and display

either 4, 10 or 20A — the Regulated Field Supply Card’s
rating.

2. The field current control loop shown above operates and

drive parameters P.184 [J20 Fld Loss Det], P.185 [J21 Field
Supply] and P.272 [E-Fld Volts Adj] are ignored.

3. The Regulated Field Loss and Field Economy circuits

become active in place of those used by the Fixed and
Enhanced Field Supply options.