Dimensions – Rockwell Automation 700-RTC Type RTC Fixed Time Solid-State Timing Relays User Manual
Page 6
![background image](/manuals/577994/6/background.png)
Publication 700-IN004C-EN-P - October 2009
6 Bulletin 700 Type RTC Fixed Time Solid-State Timing Relays
Time Delay: Fixed. Factory set at a value within }5% of time stated on
nameplate. Discrete times range from 0.1 seconds to 64 minutes, and can be
specified by user. They are not field adjustable.
Repeat Accuracy: ±1% or ±50 ms at constant voltage and temperature.
Reset Time: 25 milliseconds required.
Operating Mode: On-Delay and Off-Delay as state on nameplate. Not field
convertible.
Temperature Range: –20°C to +60°C (–4°F to +140°F)
For altitudes above 2000 meters (1.24 miles): –20°C to +50°C (–4°F to
+
122°F). For CONTINUOUS DUTY and units placed close or next to each
other (3 in a row), use –20°C to 45°C (–4°F to +113°F) or circulate air around
units.
Table 3 Contact Rating - NEMA B600, P300
Dimensions
These timing relays can be mounted directly on a panel or installed on Bulletin
700 Type MP mounting strips. Dimensions are shown below.
Mounting Dimensions
Dimensions in millimeters (inches). Dimensions are approximate and are not
intended to be used for manufacturing purposes.
Enclosure Dimensions
124mm (4.88”) x 195mm (7.69”) x 178mm (7”) deep (Cat. No. 700-N31).
AC, 50/60 Hz - NEMA B600
DC - NEMA P300
Maximum Volts
Amperes
Voltamperes
Maximum Volts
Amperes
Voltamperes
Make
Break
Make
Break
120
30
3.00
3600
360
125
250
1.1
0.55
138
240
15
1.50
480
7.5
075
600
6
0.60
Continuous Current Rating: 5 Amps
Continuous Current Rating: 5 Amps