beautypg.com

Adding or changing contact cartridges (continued), Operation – Rockwell Automation 700-RTC Type RTC Fixed Time Solid-State Timing Relays User Manual

Page 3

background image

Publication 700-IN004C-EN-P - October 2009

Bulletin 700 Type RTC Fixed Time Solid-State Timing Relays 3

Adding or Changing
Contact Cartridges
(continued)

Figure 1. Removing and Orientation of Cartridges

Operation

Table 1 outlines timer operation in both the on-delay and off-delay modes.
The red LED indicator on the front housing of the timer gives visual
indication of timing, timed out, and reset or stable timer conditions. At certain
settings, there may be a slight delay in the LED operation. The timing
sequence is not affected by this delay.

Table 1 Timer Operation

Note:

When the timer is energized or times out in the on-delay mode, an

N.O. contact may close before an N.C. contact opens; this can occur because
of inherent operating characteristics. Similarly, when the timer is de-energized
or times out in the off-delay mode, an N.C. contact may close before an N.O.
opens. Assured contact overlap or non-overlap cannot be provided in the same
device.

Orientation of cartridges

Method of removing cartridge

Projection for Keying

Insert cartridge with this end at top of timer

Operating

Mode

Power

(Terminals

L1-L2)

Voltage

(Applied to

Initiate

Terminal P)

Timer Status

Red LED

Indicator

Contact Cartridge Statue

Instantaneous

Timed

N.O

N.C

N.O

N.C

On-delay

On

No

Reset

Off

Open

Closed

Open

Closed

Yes

Timing

Flashing

Closed

Open

Open

Closed

Yes

Timed Out

On

Closed

Open

Closed

Open

Off

No

Stable

Off

Open

Closed

Open

Closed

Yes

Stable

Off

Closed

Open

Open

Closed

Off-delay

On

Yes

Reset

On

Closed

Open

Closed

Open

No

Timing

Flashing

Open

Closed

Closed

Open

No

Timed Out

Off

Open

Closed

Open

Closed

Off

No

Stable

Off

Open

Closed

Open

Closed

Yes

Stable

Off

Closed

Open

Open

Closed