Specifications (continued), Dimensions – Rockwell Automation 700-RTC_RTCR Type RTC RTCR Solid-State Relays User Manual
Page 7
![background image](/manuals/577793/7/background.png)
Publication 700-IN003C-EN-P - October 2009
Bulletin 700 Type RTC & RTCR Solid-State Relays 7
Specifications (continued)
Temperature Range: –20
°
C to +60
°
C (–4
°
F to +140
°
F)
For altitudes above 2000 meters (1.24 miles): –20
°
C to +50
°
C (–4
°
F to
+
122
°
F). For CONTINUOUS DUTY and units placed close or next to each
other (3 in a row), use –20
°
C to 45
°
C (–4
°
F to +113
°
F) or circulate air around
units.
Table 3 Contact Rating - NEMA B600, P300
Dimensions
These timing relays can be mounted directly on a panel or installed on Bulletin
700 Type MP mounting strips. Dimensions are shown below.
Mounting Dimensions
Dimensions in millimeters (inches). Dimensions are approximate and are not
intended to be used for manufacturing purposes.
Enclosure Dimensions
124mm (4.88”) x 195mm (7.69”) x 178mm (7”) deep (Cat. No. 700-N31).
On-Delay
Off-Delay
Timing
Range
(Seconds)
Switch
Position
Timing Range
(Minutes)
Switch
Position
Timing
Range
(Seconds)
Switch
Position
Timing Range
(Minutes)
Switch Position
2.0-120
8
1-64
C
2.0-120
0
1-64
4
0.4-30
9
0.25-16
D
0.4-30
1
0.25-16
5
0.2-8
A
0.06-4
E
0.2-8
2
0.06-4
6
0.05-2
B
0.015-1
F
0.05-2
3
0.015-1
7
AC, 50/60 Hz - NEMA B600
DC - NEMA P300
Maximum Volts
Amperes
Voltamperes
Maximum Volts
Amperes
Voltamperes
Make
Break
Make
Break
120
30
3.00
3600
360
125
250
1.1
0.55
138
240
15
1.50
480
7.5
075
600
6
0.60
Continuous Current Rating: 5 Amps
Continuous Current Rating: 5 Amps