Installation instructions, Technical specification, Safety ratings – Rockwell Automation 440N SensaGuard Magnetically Coded NonContact Switch (MC2) User Manual
Page 3: Physical characteristics, Outputs, Response time, Environmental, Protection
1. Installation Instructions
Installation must be in accordance with the following steps and stated specifications and should be carried out by suit-
able competent personnel. The unit is not to be used as a mechanical stop. Guard stops and guides must be fitted.
Adherence to the recommended maintenance instructions forms part of the warranty.
This device is intended to be part of the safety related control system of a machine. Before installation, a risk assess-
ment should be performed to determine whether the specifications of this device are suitable for all foreseeable opera-
tional and environmental characteristics of the machine to which it is to be fitted. Refer to Technical Specifications for
Certification information and ratings.
ATTENTION:
The presence of spare actuators compromise the integrity of the safety systems. Personal
injury or death, property damage or economic loss can result. Appropriate management con-
trols, working procedures and alternative protective measures should be introduced to control
their use and availability.
WARNING:
Do not defeat, tamper, remove or bypass this unit. Severe injury to personnel could result.
2. Technical Specification
2.1
Safety Ratings
Standards
EN1088,ISO14119, IEC/EN60947-5-3
Safety Classification
Dual contacts suitable for Cat.3 or 4 systems
Functional Safety Data
B10d: > 2 x 10
6
operations at min.
Usable for ISO 13849-1:2006 and IEC 62061. Data other
PFH
D
: > 3 x 10
7
than B10d is based on: Usage rate of 10p/10mins.,
MTTFd: > 385 years
24 hrs/day, 360 days/year, representing 51840 operations
Dual channel interlock may be suitable for performance
per year.
levels PLe or PLd (according to ISO 13849-1:2006) and for
use in SIL2 or SIL3 systems (according to IEC 62061)
Note: For up-to-date information, visit www.ab.com
depending on application characteristics.
Certifications
CE marked for all applicable directives, cULus, and TUV
2.2
Operating Characteristics (at rated temperature range)
Make, minimum
Break, maximum
Sensing distance horizontal plane of operation
10mm
25mm
Sensing distance vertical plane of operation
6mm
20mm
Typical misalignment
±4mm (see Misalignment Graphs)
Operational Current
≤
30mA + 1 Aux
Maximum # of switches, connected in series
Monitoring Relay Unit dependent (see Section 10)
Operating Voltage
24V dc +10% / -15% (see Section 9)
2.3
Physical Characteristics
Case Material
ULTRADUR
Actuator Material
ULTRADUR
Colour
Red
2.4
Outputs
Safety Output (Solid State Relay)
2 x N.C. 50mA
Auxiliary
1 x PNP N.O. 200mA
2.5
Response Time
Switch response time
5ms
Series response time
5ms
Maximum Frequency of Operation
1Hz
2.6
Environmental
Operating Temperature
-10…+55°C (+14…+131°F)
Operating Humidity
5% -95% relative
Washdown rating / Enclosure type rating
NEMA 3, 4X, 12,13, IP67, 68 & 69K
Shock & Vibration
IEC680068-2-27 30 g, 11ms
IEC680068-2-6 10…55Hz
E.M.C.
EN 61000-6-2, EN 60947-5-3
2.7
Protection
Safety Output Short-Circuit Protection
Provided by the approved safety Relays (See section 10)
Auxiliary Overload Protection
Internal Resettable Fuse
24V Supply Reverse Polarity Protection
Incorporated
Electrical Life
1 x 10
6
cycles
72697 Issue 4 EO: 28485
Magnetically Coded Non Contact Switch Installation Instructions 3