Rockwell Automation 140U Q, M frame CB Electronic RMS Trip Unit installation and operation User Manual

Page 13

background image

Table 1-1. Electronic RMS Trip Units

3 Pole

Electronic RMS Trip Unit type Catalog Numbers

Trip Unit Functions

LS

LSI

LSG

LSIG

Long Delay Fixed Ampere
Rating

¬ with

Fixed Long Delay

Adjustable ampere
Setting with fixed

Long Delay

­

l

l

l

l

l

l

l

l

Short Delay Adjustable Short

Delay Pick-up with
Short Delay Time
l

2

t Ramp

Adjustable Short
Delay Time

® with

Adjustable Short
Delay Pick-up, or

Adjustable
Instantaneous
Pick-up

®

l

l

l

l

l

l

Instant Fixed

Instantaneous
(Override)

¯

l

l

l

l

Ground Adjustable Ground
Fault Fault Pick-up with

Adjustable Ground
Fault Time

l

l

Fourth 100% rating for
Pole fourth pole
Protection

60% rating for
fourth pole

Fourth pole
unprotected

¬

Fixed rating plugs available, see Table 1-2

­ Optional four-setting adjustable rating plugs available, see Table 1-2

® Using trip unit with adjustable short delay time (LSI, LSIG), instantaneous pick-up is achieved when the lowest time delay setting

(1) is selected.

¯ A non-adjustable override setting is set at the frame withstand rating.

Page 13

40752-072(2)

Effective 6/02