ArmorStart with ArmorConnect Connectivity
Terminal Designations
ArmorConnect Cable Ratings
The ArmorConnect Power Media cables are rated per UL Type TC
600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C or
STOOW 105 °C 600V - CSA STOOW 600V FT2. For additional
information regarding ArmorConnect Power Media see the ArmorStart
User Manual.
Branch Circuit Protection Requirements for ArmorConnect™
Three-Phase Power Media
When using ArmorConnect Three-Phase Power Media, only fuses can be
used for the motor branch circuit protective device, for the group motor
installations. The recommended fuse types are the folowing: Class CC, T, or
J type fuses. A 100 A circuit breaker can be used for the motor branch
protective device, for the group motor installations when using only the
following ArmorConnect power media components: 280-M35M-M1,
280-M35F-M1, 280-T35, and 280-PWRM35*-M*. For additional
information, see the ArmorStart User Manual.
Control Power
Receptacle
Ground
Terminal
Three-Phase
Power
Receptacle
Terminal
Designations
Description
Color Code
A1 (+)
Control Power Input
Black
A2 (-)
Control Power Common
White
PE
Ground
Green/Yellow
1/L1
Line Power - Phase A
Black
2/L2
Line Power - Phase B
White
3/L3
Line Power - Phase C
Red