ArmorStart with ArmorConnect Connectivity

Terminal Designations

ArmorConnect Cable Ratings

The ArmorConnect Power Media cables are rated per UL Type TC
600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C or
STOOW 105 °C 600V - CSA STOOW 600V FT2. For additional
information regarding ArmorConnect Power Media see the ArmorStart
User Manual.

Branch Circuit Protection Requirements for ArmorConnect™
Three-Phase Power Media

When using ArmorConnect Three-Phase Power Media, only fuses can be
used for the motor branch circuit protective device, for the group motor
installations. The recommended fuse types are the folowing: Class CC, T, or
J type fuses. A 100 A circuit breaker can be used for the motor branch
protective device, for the group motor installations when using only the
following ArmorConnect power media components: 280-M35M-M1,
280-M35F-M1, 280-T35, and 280-PWRM35*-M*. For additional
information, see the ArmorStart User Manual.

Control Power

Receptacle

Ground

Terminal

Three-Phase

Power

Receptacle

Terminal
Designations

Description

Color Code

A1 (+)

Control Power Input

Black

A2 (-)

Control Power Common

White

PE

Ground

Green/Yellow

1/L1

Line Power - Phase A

Black

2/L2

Line Power - Phase B

White

3/L3

Line Power - Phase C

Red