beautypg.com

Lsdlsd msdmsd – Rockwell Automation 281G ArmorStart Distributed Motor Controller - Getting Started User Manual

Page 10

background image

10

Publication 280G-QS001A-EN-P - December 2008

Node Commissioning using Hardware

The ArmorStart is shipped with the hardware rotary switches set to a value
of (99). If the switches are set to a value of (64) or above, the device will
automatically configure itself to the software node address. If the switches
are set to a value of (63) or less, the device will be at the node address
designated by the switch configuration.

To set an address using the hardware rotary switches, simply set the
switches to the desired node address. To access the node address rotary
switches, three-phase and control power should be turned off. Then remove
the starter module from the base unit. The rotary node address switches are
located on the back side of the starter module. Change the switches to the
desired node address. Re-install the starter module to the base unit. Reapply
power and the device will re-start at the new address.

Figure 6 Rotary Node Address Configuration

System Configuration Information

The following information is provided to identify the default method for
setting up communication to the ArmorStart. Additional configuration
information and advanced settings help can be found in the
ArmorStart User Manual, Publication 280G-UM001*.

LSDLSD

MSDMSD

See Detail A

Detail A

This manual is related to the following products: