Diagnostics
EtherNet/IP LED Status
Indication
EtherNet/IP LED status and diagnostics consists of four LEDs.
• Link Activity/Status LEDS
– Ethernet Link1 Activity/Status (Port 1) – LED Color: Bicolor
(Green/Yellow), refer to Table 3
– Ethernet Link2 Activity/Status (Port 2) – LED Color: Bicolor
(Green/Yellow), refer to Table 3
• “MOD” LED – Bicolor Red/Green represents the Ethernet Module
status, refer to Table 4
• “NET” LED – Bicolor Red/Green represents the Ethernet Network
status, refer to Table 6
Figure 35 – EtherNet/IP LED
Table 3 - Link 1 or Link 2 Port Activity/Status
Link 1 or 2 Status LED
Description
Recommended Action
Off
No link established
Verify network cabling, and correct, as needed.
Green
Link established at 100 Mbps
None
Flashing green
Transmit or receive activity present at 100 Mbps
None
Yellow
Link established at 10 Mbps
None
Flashing yellow
Transmit or receive activity present at 10 Mbps
None
Table 4 - Module Status Indicator
MOD Status LED
Summary
Requirement
Steady Off
No power
If no power is supplied to the device, the module status indicator shall be
steady off.
Steady Green
Device operational
If the device is operating correctly, the module status indicator shall be
steady green.
Flashing Green
Standby
If the device has not been configured, the module status indicator shall
be flashing green.
Flashing Red
Minor fault
If the device has detected a recoverable minor fault, the module status
indicator shall be flashing red.
Note: An incorrect or inconsistent configuration would be considered a
minor fault.
Steady Red
Major fault
If the device has detected a non-recoverable major fault, the module
status indicator shall be steady red, refer to Table 5.
Flashing Green/Red
Self-test
While the device is performing its power up testing, the module status
indicator shall be flashing green/red.