Calibration, Factory default settings – Rockwell Automation 150 SMC Dialog Plus Controller - Quick Start User Manual
Page 14
![background image](/manuals/577623/14/background.png)
14
Rockwell Automation Publication 150-QS002B-EN-P - October 2011
Quick Start
Factory Default Settings
The SMC Dialog Plus controller is pre-programmed with the settings listed in
the table below.
Saving Programmed Values to Memory
After you have programmed the controller settings you
must save them to the
controller’s memory. To do this, follow the steps below:
1. Scroll to Parameter Mgmt. This is the last parameter provided in the Basic
Setup, Advanced Setup, and Calibrate programming groups.
2. Select the Store In EE option.
3. Press Enter.
Calibration
For current measurement accuracy, use the procedure below to calibrate the SMC
Dialog Plus controller to the connected motor. A clamp-on ammeter, which
provides a true rms measurement and has a published accuracy of ±1% (Fluke
model 33 or equal), is required to perform this procedure.
Parameter
Setting
Starting Mode
Soft Start
Ramp Time
10 seconds
Initial Torque
70% of locked rotor torque
Kickstart
Off
Energy Saver
Off
Stall
Off
Phase Rebalance
Off
Auxiliary Contacts
Normal
Service Factor
1.15
Overload Class
Off
Line Voltage
480 volts
Motor FLC
1.0 amps
Motor HP Rating
0.0 HP
Motor Code Letter
G
ATTENTION: Overload protection in the SMC Dialog Plus controller is
disabled from the factory. The user must program the desired overload
trip class and motor full load current rating to achieve proper protection
IMPORTANT
If control power is removed from the SMC Dialog Plus controller before
you store the programmed values to memory, all programmed values will
be lost.