600…690v ac input drives – frames 3…7 – Rockwell Automation 20G PowerFlex 750-Series EMC Plate and Cores - Frames 1…7 User Manual
Page 5

Rockwell Automation Publication 750-IN006G-MU-P - February 2014
5
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
600…690V AC Input Drives – Frames 3…7
Step
Frame Procedure
3…5
All
3…4
4
1.8 N•m (16 lb•in)
x 2 (Frame 3)
x 3 (Frames 4…5)
T20
#1
Environments with Vibration
Support Plate is recommended to
provide core support
5
Drain
Shield
Braid
Ground (PE)
5.6 N•m (50 lb•in)
Clamp
#2
M10
Drain wires must be pulled back and
wrapped in a 360 degree pattern over
the shield/braid surface. Do Not fold
the shield back.
6
IP20,
NEMA/UL Type 0
Flange Mount
to PE Stud
to PE Stud
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded
I/O Signal Shields
I/O Signal Wires
M6 (10 mm) 5.6 N•m (50 lb•in)
PE
The motor cable ground wire connects to the motor PE stud in the drive, however it should
not go through the core. Refer to Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives, publicat
for further information.
Frame 4 Shown