Input Specifications
Voltage Category
Catalog Number
110V / 120V ac
Operating Voltage Range
79V ac to 132V ac
Frequency Range
47 Hz to 63 Hz
Number of Inputs
4
Heat Dissipation
0.10 W per input
Signal Delay (max.)
On Delay: 30 ms
Off Delay: 30 ms
Off-State Voltage (max.)
20V ac
Off-State Current (max.)
1.0 mA
On-State Voltage (min.)
79V ac
On-State Current
2.0 mA at 79V ac (min.)
10.0 mA at 132V ac (max.)
Inrush Current (max.)
150 mA
Nominal Impedance
28k ohm at 50 Hz
21k ohm at 60 Hz
IEC Input Compatibility
Type 1
120V ac
193-EIMD
193-EIMD60
79V ac to 132V ac
57 Hz to 63 Hz
4
0.10 W per input
On Delay: 30 ms
Off Delay: 30 ms
20V ac
1.0 mA
79V ac
2.0 mA at 79V ac (min.)
10.0 mA at 132V ac (max.)
150 mA
21k ohm at 60 Hz
Type 1
41053-157-01 (3)
Printed in U.S.A.
PART
NO.
MATERIAL
CHG.
CHAR.
SIZE
FLAT
FOLD
-01
3
TWO SIDES PRINTED
8 1/2" W x 11" H
BODY STOCK WHITE
BODY INK BLACK
2-1/8" W x 2-3/4" H
General Specifications
Approximate Shipping Weight
(with carton)
60g
Storage Temperature
-40 to 85C
Operating Temperature (Open)
-20 to 55C
Operating Temperature (Closed)
-20 to 40C
Relative Humidity
5% to 95% non-condensing
Vibration (IEC 68-2-6)
3G
Shock (IEC 68-2-27)
30G
Maximum Altitude
2000m
Pollution Environment
Pollution Degree 2
Terminal Marking
EN 50012
Degree of Protection
1P2LX
Electrical / EMC:
The module has passed testing at the following levels:
ESD Immunity (IEC 10000-4-2)
6 kV contact, 8 kV air
Radiated Immunity (IEC 10000-4-3)
10 V/m
Fast Transient Burst (IEC 10000-4-4)
4 kV (Power), 2 kV (Control)
Surge Immunity (IEC 10000-4-5)
2 kV (L-E),1kV (L-L)
Radiated and Conducted Emissions
Class A
4
4
1
2
22-01-1
1621-01
3
1002483
41053-157
OF
N/A
N/A
N/A
REVISION
AUTHORIZATION
DR.
CHKD.
APPD.
DATE
DATE
DATE
E - DOC
LOCATION: MILWAUKEE, WISCONSIN U.S.A.
B-vertical.ai
DWG.
SIZE
SHEET
B
1
2
3
4
5
6
7
8
A
B
C
D
E
F
G
H
REFERENCE
DIMENSIONS APPLY BEFORE
SURFACE TREATMENT
(DIMENSIONS IN INCHES)
TOLERANCES UNLESS
OTHERWISE SPECIFIED
.XX:
.XXX:
ANGLES:
41053
THIS DRAWING IS THE PROPERTY OF
ROCKWELL INTERNATIONAL CORPORATION
OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,
USED OR DISCLOSED FOR ANY PURPOSE
EXCEPT AS AUTHORIZED IN WRITING BY
ROCKWELL INTERNATIONAL CORPORATION
BULLETIN 193 E3 OVERLOAD RELAY
AC INPUT INTERFACE MODULE
INSTRUCTION SHEET
------------
----------
----------
----------
------------
------------