Input Specifications

Voltage Category

Catalog Number

110V / 120V ac

Operating Voltage Range

79V ac to 132V ac

Frequency Range

47 Hz to 63 Hz

Number of Inputs

4

Heat Dissipation

0.10 W per input

Signal Delay (max.)

On Delay: 30 ms
Off Delay: 30 ms

Off-State Voltage (max.)

20V ac

Off-State Current (max.)

1.0 mA

On-State Voltage (min.)

79V ac

On-State Current

2.0 mA at 79V ac (min.)
10.0 mA at 132V ac (max.)

Inrush Current (max.)

150 mA

Nominal Impedance

28k ohm at 50 Hz
21k ohm at 60 Hz

IEC Input Compatibility

Type 1

120V ac

193-EIMD

193-EIMD60

79V ac to 132V ac
57 Hz to 63 Hz
4
0.10 W per input
On Delay: 30 ms
Off Delay: 30 ms

20V ac
1.0 mA
79V ac

2.0 mA at 79V ac (min.)
10.0 mA at 132V ac (max.)
150 mA
21k ohm at 60 Hz

Type 1

41053-157-01 (3)

Printed in U.S.A.

PART

NO.

MATERIAL

CHG.

CHAR.

SIZE

FLAT

FOLD

-01

3

TWO SIDES PRINTED

8 1/2" W x 11" H

BODY STOCK WHITE

BODY INK BLACK

2-1/8" W x 2-3/4" H

General Specifications

Approximate Shipping Weight
(with carton)

60g

Storage Temperature

-40 to 85C

Operating Temperature (Open)

-20 to 55C

Operating Temperature (Closed)

-20 to 40C

Relative Humidity

5% to 95% non-condensing

Vibration (IEC 68-2-6)

3G

Shock (IEC 68-2-27)

30G

Maximum Altitude

2000m

Pollution Environment

Pollution Degree 2

Terminal Marking

EN 50012

Degree of Protection

1P2LX

Electrical / EMC:

The module has passed testing at the following levels:

ESD Immunity (IEC 10000-4-2)

6 kV contact, 8 kV air

Radiated Immunity (IEC 10000-4-3)

10 V/m

Fast Transient Burst (IEC 10000-4-4)

4 kV (Power), 2 kV (Control)

Surge Immunity (IEC 10000-4-5)

2 kV (L-E),1kV (L-L)

Radiated and Conducted Emissions

Class A

4

4

1

2

22-01-1

1621-01

3

1002483

41053-157

OF

N/A

N/A

N/A

REVISION

AUTHORIZATION

DR.

CHKD.

APPD.

DATE

DATE

DATE

E - DOC

LOCATION: MILWAUKEE, WISCONSIN U.S.A.

B-vertical.ai

DWG.

SIZE

SHEET

B

1

2

3

4

5

6

7

8

A

B

C

D

E

F

G

H

REFERENCE

DIMENSIONS APPLY BEFORE

SURFACE TREATMENT

(DIMENSIONS IN INCHES)

TOLERANCES UNLESS

OTHERWISE SPECIFIED

.XX:

.XXX:

ANGLES:

41053

THIS DRAWING IS THE PROPERTY OF

ROCKWELL INTERNATIONAL CORPORATION

OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,

USED OR DISCLOSED FOR ANY PURPOSE

EXCEPT AS AUTHORIZED IN WRITING BY

ROCKWELL INTERNATIONAL CORPORATION

BULLETIN 193 E3 OVERLOAD RELAY

AC INPUT INTERFACE MODULE

INSTRUCTION SHEET

------------

----------
----------
----------

------------

------------