Monitoring the drivelogix controller leds – Rockwell Automation 20D DriveLogix Controller for PowerFlex 700S Phase I Drives User Manual
Page 16
![background image](/manuals/577161/16/background.png)
16
DriveLogix Controller for PowerFlex 700S Phase I Drives
Monitoring the DriveLogix
Controller LEDs
!
ATTENTION: The controller LEDs are only operational when
the drive is energized, and only visible with the drive door open.
Servicing energized equipment can be hazardous. Severe injury
or death can result from electrical shock, burn or unintended
actuation of controlled equipment. Follow Safety related
practices of NFPA 70E, ELECTRICAL SAFETY FOR
EMPLOYEE WORKPLACES. DO NOT work alone on energized
equipment!
Type
Name
Color
State
Description
Daughter card
LEDs
PORT
Green
–
Status of DPI port internal communications (if
present).
MOD
Yellow
–
Status of communications module (when
installed).
NET A
Red
–
Status of network (if connected).
NET B
Red
–
Status of secondary network (if connected).
NET A
OFF
No power,
Host is faulted,
Host is holding daughter card in reset.
Red Steady Major
Fault
Red Flashing Minor
Fault
Green Flashing No
connections
established
Green Steady Connections
established
NET B
OFF
No power,
Host is faulted,
Host is holding daughter card in reset.
Red Steady Major
Fault
Red Flashing Minor
Fault
Green Flashing No
connections
established
Green Steady Connections
established