Control I/O Terminal Designations
No. Signal
Default
Description
Param.
R1
Relay N.O.
Fault
Normally open contact for output relay.
A055
R2
Relay Common
–
Common for output relay.
R3
Relay N.C.
Fault
Normally closed contact for output relay.
A055
Analog Output Select
DIP Switch
0-10V
Sets analog output to either voltage or current. Setting must match
A065 [Analog Out Sel].
Sink/Source
DIP Switch
Source (SRC)
Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch
setting.
01
Stop
(1)
Coast
The factory installed jumper or a normally closed
input must be present for the drive to start.
02
Start/Run FWD
Not Active
I/O Terminal 03 is fully programmable. Program with
E202 [Digital Term 3]. To disable reverse operation,
see A095 [Reverse Disable].
P036, P037
03
Digital Term 3
Not Active
P036, P037,
A095, E202
04
Digital Common
–
For digital inputs. Electronically isolated with digital
inputs from analog I/O and opto outputs.
05
Digital Input 1
Preset Freq
Program with A051 [Digital In1 Sel].
A051
06
Digital Input 2
Preset Freq
Program with A052 [Digital In2 Sel].
A052
07
Digital Input 3
Local
Program with A053 [Digital In3 Sel].
A053
08
Digital Input 4
Jog Forward
Program with A054 [Digital In4 Sel].
A054
09
Opto Common
–
For opto-coupled outputs. Electronically isolated with
opto outputs from analog I/O and digital inputs.
11
+24V DC
–
Referenced to Digital Common.
Drive supplied power for digital inputs.
Maximum output current is 100mA.
12
+10V DC
–
Referenced to Analog Common.
Drive supplied power for 0-10V external
potentiometer.
Maximum output current is 15mA.
P038
13
±10V In
(2)
Not Active
For external 0-10V (unipolar) or ±10V (bipolar) input
supply (input impedance = 100k ohm) or
potentiometer wiper.
P038,
A051-A054,
A123, A132
14
Analog Common
–
For 0-10V In or 4-20mA In. Electronically isolated
with analog inputs and outputs from digital I/O and
opto outputs.
15
4-20mA In
Not Active
For external 4-20mA input supply
(input impedance = 250 ohm).
P038,
A051-A054,
A132
16
Analog Output
OutFreq 0-10
The default analog output is 0-10V. To covert to a
current value, change the Analog Output Select DIP
Switch to 0-20mA. Program with A065 [Analog Out
Sel]. Max analog value can be scaled with A066
[Analog Out High].
Maximum Load:
4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)
A065, A066
17
Opto Output 1
MotorRunning
Program with A058 [Opto Out1 Sel]
A058, A059,
A064
18
Opto Output 2
At Frequency
Program with A061 [Opto Out2 Sel]
A061, A062,
A064
19
RS485 (DSI) Shield –
Terminal should be connected to safety ground - PE
when using the RS485 (DSI) communications port.
(1)
See Footnotes (1) and (6) on page 11.
(2)
0-10V In and 4-20mA In are distinct input channels and may be connected simultaneously.
Inputs may be used independently for speed control or jointly when operating in PID mode.