beautypg.com

Rockwell Automation 22-COMM PowerFlex 4-Class DSI (Drive Serial Interface) Network Communication Adapter User Manual

Page 3

background image

3

Figure 2 Connecting DSI Ports with Internal Interface Cable

Item Description

DSI Connector

15.24 cm (6 in.) Internal Interface cable

Network cable

PowerFlex 400 Class Frame D and Higher

C. With the adapter board right side up, remove its mounting screw from

the lower left hole. Save the screw for mounting in step F.

D. Connect the Internal Interface cable to the DSI port on the drive (see

Figure 3

).

E. With the adapter board oriented bottom side up, route the Internal

Interface cable under the adapter, and then to the mating DSI connector
on the adapter.

F. Install the adapter, bottom side up, to the right side of the display board

by snapping it into place. Then insert the adapter mounting screw into
the lower left hole on the board.

Important: Tighten the mounting screw in the adapter’s lower left hole

to ground the adapter to the drive.

(22-COMM-E EtherNet/IP

Adapter shown as example)

PowerFlex 40 Drive
(Frame C shown as

example with cover removed)

Back of Required

Special Drive Cover