VERTICAL HIGH OUTPUT

VHC-IOM-00 01-19-09

INSTALLATION AND

MAINTENANCE INSTRUCTIONS

5

f

o

5

e

g

a

P

8.7

Electric Heater(s) (Optional)

8.7.1

The heater is fastened to the discharge collar at the blower outlet with sheet metal

screws.

8.7.2

In case of heater failure, follow the procedure described below:

8.7.3

Disconnect all power sources before attempting to open the unit. Check all electrical

wiring to ensure the unit is fully isolated.

8.7.4

Unscrew the front access panel and expose the heater(s).

8.7.5

If the thermal cut-out switch is defective, disconnect the electrical wires and unscrew

it from the heater assembly. Obtain a replacement from TITUS and

reinstall.

8.7.6

If the heating element (the spiral resistance wire) is burned out, unscrew the heater

assembly from the fan deck, disconnect the terminals and replace with a new heater

obtained from TITUS.

***When contacting TITUS for replacement parts, always

refer to the complete Model, Order and Line numbers on the Serial

Plate located on the blower housing.