Titus T3SQ-2 Thermostat Operating Manual User Manual
Page 5
Thermostat Operating Manual - T3SQ-2
5
Press the enter button and observe the ‘L’ stationary
and the zone number flashing.
Using the up/down arrows, select the next zone
number and press enter.
Using the same procedure set up each diffuser in the
control zone of interest.
A maximum of fifteen control zones (one diffuser per
zone) can be set up. By the same token a minimum
of one zone containing from one to fifteen diffusers
(slaves) can also be set up.
Press enter again to exit the last zone setup.
To advance to the next menu, press the menu button.
SUB M
CONTROL INPUT SELECT
The next function is to select the setpoint, control and
supply air temperatures for a particular control zone. As
mentioned, to use this function the setup module must
be connected to a diffuser in the control zone of interest.
On a default system with only one wall-stat or one analog
module connected to a control zone this function won’t be
required.
The display will indicate ‘tS’ in the top left character
display.
The character display will indicate the current status of
the three control inputs as follows:
‘o’
-
indicates ‘on-board’ for analog module.
‘r’
-
indicates ‘remote’ for wall-stat
‘-‘
-
indicates not selected
Keep the enter button pressed until the unit beeps. The
first character will flash with the display indicating ‘t’ for
control temperature selection.
Pressing the up/down arrows will toggle between
remote or on-board temperature selections. Be sure to
select a valid option, ie when selecting ‘remote’ there
must be a wall-stat connected to that particular control
zone.
Press enter and the character ‘S’ will show to indicate
setpoint selection. The up/down arrows will toggle this
function.
Press enter to select the supply air input, character ‘C’.
The arrow buttons will toggle between ‘o’, ‘r’ and ‘-‘ if
supply air measurement is not required.
On pressing enter again the three characters will flash
until the system has accepted the new setup.
Press the menu button to exit this function.
To advance to the next menu, press the menu button.
SUB M
SETPOINT ADJUST
The next function displayed is setpoint adjust with the ‘SP’
icon on.
Note the setup module must be plugged into the
control zone of interest for this function.
The top left character display will indicate ‘S1’ for
setpoint 1. Setpoint 2, or the back off setpoint is not
adjustable with this unit.
Press the up/down arrow to select the required
setpoint. The digits will flash.
Press enter. The display will flash ‘---‘ until the new
setpoint has been accepted.
Press the menu button to exit this function and revert
to the main menu.