beautypg.com

Titus T3SQ-2 Thermostat Operating Manual User Manual

Page 5

background image

Thermostat Operating Manual - T3SQ-2

5

Press the enter button and observe the ‘L’ stationary

and the zone number flashing.

Using the up/down arrows, select the next zone

number and press enter.

Using the same procedure set up each diffuser in the

control zone of interest.

A maximum of fifteen control zones (one diffuser per

zone) can be set up. By the same token a minimum

of one zone containing from one to fifteen diffusers

(slaves) can also be set up.

Press enter again to exit the last zone setup.

To advance to the next menu, press the menu button.

SUB M

CONTROL INPUT SELECT

The next function is to select the setpoint, control and

supply air temperatures for a particular control zone. As

mentioned, to use this function the setup module must

be connected to a diffuser in the control zone of interest.

On a default system with only one wall-stat or one analog

module connected to a control zone this function won’t be

required.

The display will indicate ‘tS’ in the top left character

display.

The character display will indicate the current status of

the three control inputs as follows:

‘o’

-

indicates ‘on-board’ for analog module.

‘r’

-

indicates ‘remote’ for wall-stat

‘-‘

-

indicates not selected

Keep the enter button pressed until the unit beeps. The

first character will flash with the display indicating ‘t’ for

control temperature selection.

Pressing the up/down arrows will toggle between

remote or on-board temperature selections. Be sure to

select a valid option, ie when selecting ‘remote’ there

must be a wall-stat connected to that particular control

zone.

Press enter and the character ‘S’ will show to indicate

setpoint selection. The up/down arrows will toggle this

function.

Press enter to select the supply air input, character ‘C’.

The arrow buttons will toggle between ‘o’, ‘r’ and ‘-‘ if

supply air measurement is not required.

On pressing enter again the three characters will flash

until the system has accepted the new setup.

Press the menu button to exit this function.

To advance to the next menu, press the menu button.

SUB M

SETPOINT ADJUST

The next function displayed is setpoint adjust with the ‘SP’

icon on.

Note the setup module must be plugged into the

control zone of interest for this function.

The top left character display will indicate ‘S1’ for

setpoint 1. Setpoint 2, or the back off setpoint is not

adjustable with this unit.

Press the up/down arrow to select the required

setpoint. The digits will flash.

Press enter. The display will flash ‘---‘ until the new

setpoint has been accepted.

Press the menu button to exit this function and revert

to the main menu.