Thermostat Operating Manual - T3SQ-2

4

O P E R AT I N G M A N U A L

Thermostat

To change the open end-stop position, press the up/

down arrows for the required position and press enter.

The display will flash ‘---‘ until the new parameter is

accepted by the system.

Should the disk be outside the end-stop range it will

manually drive the diffusers in that control zone into

range.

To advance to the next menu, press the menu button.

SUB M

CONTROL DISK CLO

OP

The display will show the close end-stop disk position in

percentage, with the top left character display indicating

‘dr’. The up arrow and bar will flash to indicate ‘close end-

stop’

To change the close end-stop position, press the up/

down arrows for the required position and press enter.

The display will flash ‘---‘ until the new parameter is

accepted by the system.

Should the disk be outside the end-stop range it will

manually drive the diffusers in that control zone into

range.

To advance to the next menu, press the menu button.

SUB M

HEATER OUTPUT

The display will show the current heater output in percent-

age, with the top left character display indicating ‘Ht’.

To manually drive the heater output, press the up/

down arrows for the required position and press enter.

The heater icon will flash to indicate the heater is

manually controlled.

The character display will indicate zero until the new

value is accepted and the heater in that zone controlled

to the new value.

To advance to the next menu, press the menu select

button. The control will revert back to automatic.

SUB M

CONTROL ZONE S

LOO

To bind a diffuser to a control zone the following steps is

required:

The top left character display will indicate ‘LS’ for Loop

Select.

Keep the enter button pressed until the unit beeps.

The menu display ‘L and a zone number, ‘00’. If the

zone has been set up previously, that particular zone

number will display iso the ‘00’.

Press enter again and the zone number will flash.

Use the up/down arrow to select a zone number. On a

new installation always start with zone ‘1’.

Press enter and observe the ‘L’ starting to flash.

Go to the first diffuser in that zone and press the

button on the MLM MD board, normally situated on the

trim disk.

After a few seconds the Setup Module will beep and

the flashing LED on the MLM MD board will stay

switched on momentarily – both to indicated the

diffuser is set up for that control zone.

Go to the next diffuser in that zone and press the

button again and observe the same result. All the while

the ‘L’ indicator will flash and the zone number will be

on permanently.

Continue the process until all the diffusers in the

control zone has been selected.