Thermostat Operating Manual - T3SQ-2
4
O P E R AT I N G M A N U A L
Thermostat
To change the open end-stop position, press the up/
down arrows for the required position and press enter.
The display will flash ‘---‘ until the new parameter is
accepted by the system.
Should the disk be outside the end-stop range it will
manually drive the diffusers in that control zone into
range.
To advance to the next menu, press the menu button.
SUB M
CONTROL DISK CLO
OP
The display will show the close end-stop disk position in
percentage, with the top left character display indicating
‘dr’. The up arrow and bar will flash to indicate ‘close end-
stop’
To change the close end-stop position, press the up/
down arrows for the required position and press enter.
The display will flash ‘---‘ until the new parameter is
accepted by the system.
Should the disk be outside the end-stop range it will
manually drive the diffusers in that control zone into
range.
To advance to the next menu, press the menu button.
SUB M
HEATER OUTPUT
The display will show the current heater output in percent-
age, with the top left character display indicating ‘Ht’.
To manually drive the heater output, press the up/
down arrows for the required position and press enter.
The heater icon will flash to indicate the heater is
manually controlled.
The character display will indicate zero until the new
value is accepted and the heater in that zone controlled
to the new value.
To advance to the next menu, press the menu select
button. The control will revert back to automatic.
SUB M
CONTROL ZONE S
LOO
To bind a diffuser to a control zone the following steps is
required:
The top left character display will indicate ‘LS’ for Loop
Select.
Keep the enter button pressed until the unit beeps.
The menu display ‘L and a zone number, ‘00’. If the
zone has been set up previously, that particular zone
number will display iso the ‘00’.
Press enter again and the zone number will flash.
Use the up/down arrow to select a zone number. On a
new installation always start with zone ‘1’.
Press enter and observe the ‘L’ starting to flash.
Go to the first diffuser in that zone and press the
button on the MLM MD board, normally situated on the
trim disk.
After a few seconds the Setup Module will beep and
the flashing LED on the MLM MD board will stay
switched on momentarily – both to indicated the
diffuser is set up for that control zone.
Go to the next diffuser in that zone and press the
button again and observe the same result. All the while
the ‘L’ indicator will flash and the zone number will be
on permanently.
Continue the process until all the diffusers in the
control zone has been selected.