Installation, Venting – Regency Panorama P36 Medium Gas Fireplace User Manual
Page 19
FPI P36-4 Zero Clearance Direct Vent Gas Fireplace
19
INSTALLATION
VENTING
DIRECT VENT SYSTEM (FLEX)
HORIZONTAL TERMINATIONS ONLY
These venting systems, in combination with the P36 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by
Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in the "Exterior Vent
Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kit (Part # 946-515) includes all the parts needed to install the P36 with a maximum run of 4 feet.
1)
6-7/8" dia. fl exible liner (4 ft. length)
2)
4" dia. fl exible liner (4 ft. length)
3)
spring spacers (4)
4)
thimble (2)
5)
AstroCap termination cap (1)
6)
screws (12)
7)
tube of Mill Pac (1)
8)
plated screws (8)
9)
screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
1)
6-7/8" dia. fl exible liner (10 ft. length)
2)
4" dia. fl exible liner (10 ft. length)
3)
spring spacers (7)
4)
thimble (2)
5)
AstroCap termination cap (1)
6)
screws (12)
7)
tube of Mill Pac (1)
8)
plated screws (8)
9)
screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
If longer runs are needed, the FPI Direct
Vent system (Flex) # 946-516 includes all
the parts needed to install the P36 with a
maximum 10' run.
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from FPI may be used for Flex installations.
3) If you are installing the P36 into a FPI Cabinet Mantel Kit, use the minimum horizontal vent height (centre-line of 40-1/2"). Remember
to include the mantel base (3" in height) in your calculations and to maintain the 2" clearance to the underside of the mantel top.