Installation, Regency, Mantel leg clearances – Regency Panorama P36 Medium Gas Fireplace User Manual

Page 14: Series combustible mantel clearances

background image

14

FPI P36-4 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

REGENCY

®

MANTEL LEG CLEARANCES

Combustible mantel leg clearances as per diagram:

Maximum 1-1/2" projection
at 2" minimum clearance.

REGENCY

®

SERIES COMBUSTIBLE MANTEL CLEARANCES

Because of the extreme heat this fi replace emits, the mantel clearances are critical.
Combustible mantel clearances from top of unit are shown in the diagram below.

Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible

board.

These drawings are to scale at 1:6 (one inch = 6 inches)
Mantel can be installed anywhere in shaded area or higher using the above scale.

Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint

may discolour.