Installation, Minimum clearances to combustibles, Combustible mantel clearances – Regency Horizon HZI234E Small Gas Insert User Manual

Page 12

background image

12

Regency

®

HZI234E Direct Vent Gas Insert

INSTALLATION

MINIMUM CLEARANCES TO

COMBUSTIBLES


Side Walls

A 8" (203 mm)*

Ceiling

B 56" (1422 mm)

Min. Mantel Height C 15-1/2" (394 mm)

see Diagram 1

Max. Mantel Depth D 12" (305 mm)

see Diagram 1

Alcove Width

E 60" (1524 mm)

Alcove Depth

F 36" (914 mm)

* Alcove side wall must have a min. of 8" clearance.

COMBUSTIBLE MANTEL

CLEARANCES

Because of the extreme heat this fi replace emits, the mantel clear-
ances are critical.
Combustible mantel clearances from top of door frame
are shown in the diagram below. Mantel may be installed anywhere in the
shaded area or higher.

Note: A non-combustible mantel may be installed at a lower

height.

Note: Ensure the paint that is used on the mantel and the facing is

“heat resistant” or the paint may discolour.

D

E

F

A

B

C

56”

to ceiling

15-5/8” (397mm)

to floor

12” Mantel

1” Mantel

4” Mantel

24-1/2”

Top of Door Frame

15-1/2”

17-1/2”

22

24

Unless otherwise stated the clearances listed below are Minimum distances
to combustible materials. Please Note: A major cause of chimney
related fi res is due to a failure to maintain required clearances (air
space) to combustible materials. It is of the greatest importance
that this insert and vent system be installed only in accordance with
these instructions.

Diagram 1